Installation, Operation, and Maintenance Instructions
Receiving and Handling
Upon receiving dampers, check for both obvious and
hidden damage. If damage is found, record all necessary
information on the bill of lading and file a claim with
the final carrier. Check to be sure that all parts of the
shipment, including accessories, are accounted for.
Dampers must be kept dry and clean. Indoor storage
and protection from dirt, dust and the weather is highly
recommended. Do not store at temperatures in excess
of 100°F (38°C).
Warranty
Greenheck warrants this equipment to be free from
defects in material and workmanship for a period of one
year from the purchase date. Any units or parts which
prove to be defective during the warranty period will
be repaired or replaced at our option. Greenheck shall
not be liable for damages resulting from misapplication
or misuse of its products. Greenheck will not be
responsible for any installation or removal costs.
Greenheck will not be responsible for any service work
or backcharges without prior written authorization.
Due to continuing research, Greenheck reserves the right to change specifications without notice.
This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when
the job is complete.
Document Number 461337
OFD-XXX, and OSSFD-XXX Series
11/2 Hour Combination Fire Smoke or Curtain Fire Dampers
OFSD-XXX, ODFD-XXX, OFD-XXX, and OSSFD-XXX
series dampers are intended for installation in accordance
with combination fire smoke dampers requirements
established by:
NFPA National Fire Protection Association
IBC International Building Codes
New York City (MEA listing # 260-91-M)
California State Fire Marshal
"UL Classified (see complete marking on product)"
"UL Classified to Canadian safety standards (see
complete marking on product)"
All wiring shall be done in accordance with the National
Electrical Code ANSI/NFPA-70 latest edition, any local
codes that may apply, and wiring diagrams developed
in compliance with the job or project design and
specifications.
Improper installation, adjustment, alteration, service
or maintenance can cause property damage, injury or
death. Read the installation, operating, and maintenance
instructions thoroughly before installing or servicing this
equipment.
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
Verify power before wiring actuator. Greenheck is not
responsible for any damage to, or failure of the unit
caused by incorrect field wiring. To avoid causing death
or serious bodily harm to building occupants, follow all
instructions carefully. Dampers must close completely to
preserve the integrity of the fire smoke separation.
OFSD-XXX, ODFD-XXX,
Out of Wall or Out of Floor
Vertical or Horizontal Mount
NFPA Standards 80, 90A, 92A, 92B, 101, & 105
Listing #3225-0981:103 & 3230-0981:104
UL Standard 555 & 555S (Classification R13317)
Electrical Guidelines
Safety Warning:
Safety Caution!

Advertisement

Table of Contents
loading

Summary of Contents for Greenheck ODFD Series

  • Page 1 Due to continuing research, Greenheck reserves the right to change specifications without notice. This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when...
  • Page 2: Table Of Contents

    Table of Contents Pre-Installation Guidelines ..........................2 Installation ..............................2-6 • Clearances Requirements ......................... 3 • Duct to Sleeve Connections ......................9 • Securing the Damper/Sleeve Assembly to Wall and Floor Openings ........9-10 • Actuator Connections ........................10 • Recommended Preparation of Openings in Wood and Metal Stud Walls ........10 •...
  • Page 3: Clearances Requirements

    the header, sill and jamb framing members. Screw into rear portion of the studs so as to avoid space conflicts with the grille assembly. Factory Supplied Thermal Blanket 1. DAMPER IS INSTALLED OUTSIDE OF WALL PLANE Factory Supplied Thermal Blanket OFSD-XXX Grille (Supplied...
  • Page 4 Figure 2 Concrete or Wood Masonry Wall Stud 7 1/2 in. Concrete or Wood (191mm) Masonry Damper max. Stud Steel Stud Wall Flange Flange 7 1/2 in. (191mm) maximum Damper Steel Stud Factory Supplied Alternate Flange Thermal Blanket Retaining Retaining Angle Angle Location...
  • Page 5 Figure 2 cont... Masonry or Wood Concrete Wall Stud Concrete or Wood Stud Masonry Wall 7 1/2 in. (191mm) 7 1/2 in. (191mm) Metal maximum max. Stud Damper Damper Factory Supplied Alternate Retaining Factory Supplied Thermal Blanket Angle Location Thermal Blanket Retaining Retaining Retaining...
  • Page 6 Figure 2 cont..Wood Stud 7 1/2 in.(191mm) Maximum Damper Metal Stud Masonry or Concrete 7 1/2 in. (191mm) Wood Stud Damper maximum Factory Supplied Thermal Blanket Steel Retaining Retaining Stud Angle Angle Flange Type B2- Vertical Mount, Thru Duct with Two Retaining Angles Factory Supplied Thermal Blanket...
  • Page 7 Figure 2 cont..7 1/2 in. (191mm) Wood maximum Damper Stud Concrete or Metal Stud Masonry 7 1/2 in. (191mm) maximum Damper Concrete or Masonry Factory Supplied Thermal Blanket Retaining Factory Supplied Angle Thermal Blanket Alternate Retaining Retaining Angle Location Angle Alternate Retaining Angle Location...
  • Page 8 Figure 2 cont..Wood Wood Stud 7 1/2 in. (191mm) Stud maximum 7 1/2 in. (191mm) Damper maximum Metal Stud Flange Concrete or Concrete or Masonry Masonry Factory Supplied Retaining Metal Thermal Blanket Angle Retaining Stud Angle Factory Supplied Thermal Blanket Type C2- Vertical Mount, Thru Duct with Type C2- Vertical Mount, Duct Terminates Two Retaining Angles...
  • Page 9: Duct To Sleeve Connections

    Figure 2 cont..Wood Stud 3. DUCT TO SLEEVE CONNECTIONS Dampers are supplied with actuators (on applicable Metal Stud 7 1/2 in. (191mm) models) and sleeves from the factory and can be installed maximum without the need for additional field installed sleeves. Sleeve gauges of 20-14 (.9mm - 2mm) are to be used.
  • Page 10: Actuator Connections

    4. SECURING THE DAMPER/SLEEVE ASSEMBLY TO WALL OPENINGS continued..Retaining Angle • Retaining angles must be attached to the sleeve using Thermal Blanket one or more of the following methods of attachment: (installed around entire outside • Tack or spot welds surface of sleeve) •...
  • Page 11: Breakaway Connections

    Damper exposed steel surfaces need Sleeve not be covered with gypsum wallboard. Metal Stud Construction Wooden Stud Construction Gypsum Wallboard Gypsum Wallboard Stud or Runner Stud or Runner Retaining Retaining Angle Angle 1 in. Min. 1 in. Min. In metal stud construction, Damper exposed steel surfaces need Sleeve...
  • Page 12: Maintenance

    Add power supply operate Our Commitment As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties.