Extinguishing unit

Advertisement

Num
Name
1
INALL1
2
GND
3
INALL2
4
INATTM
5
GND
6
INPROLE
7
INMANU
8
GND
9
ININTEM
10
INPRESS
11
GND
12
INFLUSS

2.2 - DESCRIPTION OF INPUTS

The following activation window applies to each input on the terminal board. The only exception is the three inputs flow
switch, pressure switch and manual activation, where it is possible, from the configuration menu (CONF button), to
exchange the rest window with the alarm window (for NC or NO type inputs).
In the default configuration, all inputs are balanced with a 5.4kΩ nominal "End-of-Line" resistor, Rest value, obtained
from the series of two 2.7kΩ resistors. An NO contact is applied to one of the two resistors at rest. The input is activated
when the contact is closed and the nominal resistance drops to 2.7kΩ, the Activation value.
A resistance drift control algorithm is applied to each input, and if the resistance value falls within the resistance ranges
L, M and H, an input level fault '... undetermined low', '... undetermined medium' and '... undetermined high' is provided.
Other faults that can be signalled by an input are: "short-circuited", "open" with obvious meaning, in addition diagnostics
in "fault" and "unstable". In the latter case it means that the input is constantly changing between states but does not
remain there long enough.
Short circuit
1K
N.B. The maximum number of devices that can be connected to the line (manual override controls, emergency
override and emergency stop controls) depends on the distance from the unit and their power consumption.
UDS-4
UDS-4_manu
Notes/Relays
NA
NA
NA,[NA|NC].
NA
NA
NA
NA,[NA|NC].
NA,[NA|NC].
L
Activation
1k2
3k8
Installation and user manual
M--203.1-UDS4N-ENG Rev A.1
CNIN
Description
Alarm 1 (from conventional control unit L1)
(controlled entry)
Alarm 2 (from conventional control unit L2)
(controlled entry)
Device Manual Activation Power Off
(controlled entry)
Emergency Extension Device
(controlled entry)
Manual shutdown only
(controlled entry)
Emergency Interruption Device
(controlled entry)
Pressure switch
(controlled entry)
Flow switch
(controlled entry)
M
Rest
4k2
H
Cut
6k5
7k
PAGE - 5
NOTIFIER ITALIA