PEERLESS PUREFIRE PFW-199 Installation, Operation & Maintenance Manual page 28

Gas hot water supply boiler
Table of Contents

Advertisement

FUEL PIPING
b. Turning the throttle screw clockwise will decrease
the gas flow (decreasing CO
counterclockwise will increase the gas flow rate
(increasing CO
screw show + and – indicating this operation.
c. The recommended CO
5.4. In no case should the boiler be allowed to
operate with CO emissions above 150 ppm.
Table 5.4: Recommended Combustion Settings
Carbon Dioxide (CO
)
2
Carbon Monoxide (CO)
Excess Oxygen (O
)
2
Excess Air
26
) and turning it
2
). Markings adjacent to the throttle
2
settings are given in Table
2
Natural Gas
Low Fire
8.8% to 10.0%
< 50 ppm
3.4% to 5.4%
17.3% to 31.0%
2. Refer to Section 3, Venting and Air Intake for
information on obtaining vent samples from this boiler.
High Fire
8.5% to 9.5%
9.8% to 11.0%
< 100 ppm
4.2% to 6.0%
4.2% to 6.0%
22.4% to 35.8%
22.4% to 35.8%
LP Gas
Low Fire
High Fire
9.5% to 10.5%
< 50 ppm
< 100 ppm
4.9% to 6.5%
27.3% to 40.1%