5.2 Connection diagram

Supply connection
Fig. 7
Connection diagram
Warning
Wires connected to
– supply terminals,
– outputs NC, NO, C and
– start/stop input
must be separated from each other
and from the supply by reinforced
insulation.
All wires connected to a terminal
block must be tied up at the
terminals.
Concerning demands on signal wires and signal
transmitters, see section 11. Technical data.
A connection example can be found on page 342.
10
Signal output
1
NC NO C
L
N
NC NO C
Start/stop input
8
2
3
S
T
O
P
Note:
If no external on/off switch is connected, the
connection across terminals STOP and
be maintained.
All cables used must be heat-resistant up to
+85 °C.
All cables used must be installed in accordance
with EN 60204-1 and EN 50174-2: 2000.
If a GENI module is fitted, the screen must be
connected to
. See page 344.