Outer Panels Si001407EB 1. Outer Panels Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the screw of The stop valve cover is the stop valve cover. united with the shield plate.
Page 5
Si001407EB Outer Panels Step Procedure Points Release the outdoor Be careful not to cut your Outdoor temperature thermistor temperature thermistor. finger on the fins of the outdoor heat exchanger. Lift up the guard net and remove it. (R20262) Remove the 3 screws, and then the wire fixture.
Fan Motor Si001407EB 2. Fan Motor Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the nut of the You can remove the fan outdoor fan. without removing the right side panel.
Page 7
Si001407EB Fan Motor Step Procedure Points Remove the screw and, When reassembling, fit the 2 then the fan motor lower hooks into the bottom fixing frame. frame. Hook (R20269) Fan motor fixing frame Unfasten the 2 hooks and release the fan motor lead wire.
Electrical Box Si001407EB 3. Electrical Box Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Cut the clamp. Disconnect the [S30]: compressor connector [S30]. Disconnect the [S40]: overload protector connector [S40].
Page 9
Si001407EB Electrical Box Step Procedure Points Disconnect the 2 Brown connectors for the Orange reactor. Reactor (R20275) Disconnect the [S90]: thermistors [S90] Clamp connector [S90]. Cut the clamp. (R20276) Lift up and remove the electrical box. Electrical box (R23489) Removal Procedure...
Thermistor ASSY Si001407EB 4. Thermistor ASSY Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Release the discharge Be careful not to lose the pipe thermistor. fixture for the thermistor. Fixture (R20430) Discharge pipe...
Si001407EB 5. PCB Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the screw on You can remove the main the terminal board. PCB when you disconnect the lead wires on the terminal board without removing the terminal board.
Page 12
Si001407EB Step Procedure Points Remove the 4 screws. (R20284) Unfasten the 4 hooks Hook and remove the PCB. Hook (R23494) Removal Procedure...
Si001407EB Reactor / Partition Plate 6. Reactor / Partition Plate Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1. Remove the reactor. Remove the screw. Slide the reactor to the left and remove the reactor.
Sound Blankets Si001407EB 7. Sound Blankets Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points Remove the sound Since the piping ports are Sound blanket (top) blanket (top). torn easily, remove the sound blankets carefully.
Si001407EB Capillary Tube 8. Capillary Tube Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Be careful not to get yourself burnt with the pipes and other parts that are heated by the gas brazing machine.
Page 16
Capillary Tube Si001407EB Step Procedure Points Disconnect the lead Protection bushing wires of the compressor and the overload protector. Remove the protection bushing. W (red) Overload protector V (yellow) W (blue) (R20293) Remove the putties, if any. Heat up the 2 brazed parts and withdraw the piping with pliers.
Si001407EB Compressor 9. Compressor Warning Be sure to wait for 10 minutes or more after turning off all power supplies before disassembling work. Be careful not to get yourself burnt with the pipes and other parts that are heated by the gas brazing machine.
Page 18
Compressor Si001407EB Step Procedure Points Disconnect the lead Protection bushing wires of the compressor and the overload protector. Remove the protection bushing. W (red) Overload protector V (yellow) W (blue) (R20293) Remove the putties, if any. Heat up the 2 brazed parts and disconnect the pipings.
Page 19
Revision History Month / Year Version Revised contents 05 / 2014 Si001407E First edition 11 / 2015 Si001407EA Model addition: RKP25/35QRV16, RKPA25/35QRV16, RKPD25/35QRV16 07 / 2016 Si001407EB Model addition: RKH35QRV16, RKH35RRV16...
Page 20
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
Need help?
Do you have a question about the RKH35QRV16 and is the answer not in the manual?