Download Print this page

Siemens SINAMICS V50 Operating Instructions Manual page 14

Advertisement

Installation
4.6 SINAMICS V50 Standard configuration of control circuit terminals
Type
Termin
Digital
X1
input
X3
X4
X5
COM
Digital
output
24V
Y1
DO
COM
Analog
input
10V
AI1
AI2
GND
Analog
output
AO1
SINAMICS V50 converter
13
Operating Instructions, 04/2022, FW V1.0, A5E44777205B AB
Terminal function
Multi-functional
input terminals 1 -3
Multi-functional
input or Single pulse
input 4, 5
Multi-functional
input terminals
common end
24V
Open collector
output 1
Open collector or
high-speed pulse
output
Open collector
output common
end
Analog input
reference voltage
Analog input
channel 1
Analog input
channel 2
Analog grounding
Analog output 1
Technical specification
Optical-isolator input Frequency
range: 0 - 200Hz
Voltage range: 0 - 24V
Multi-functional input: same as X1 -
X3
Single Pulse input: 0.1Hz - 50kHz
Voltage range: 0 - 24V
Internal isolated with GND
24V±5%, Maximum load :200mA,
with overload and short circuit
protection
Optical-isolator output maximum
output current: 50mA
Output voltage range: 0 - 24V
Output frequency: 0 - 50kHz
Can be used as the normal open
collector.
Internal isolated with GND
Open circuit voltage up to 11V;
Internal isolated with COM;
Maximum load 30mA, with overload
and short circuit protection
Input Voltage range: 0 - 10V
Input impedance: 100kOhm
Input Voltage range: 0 - 10V
Input impedance: 100kOhm
Input current range: 0-30mA
Current input impedance: 500Ohm,
0 - 20mA or 0 - 10V analog input can
be selected through DIP switch
SW2
Internal isolated with COM
0/4 - 20mA: Allow output impedance
200-500Ohm
0-10V: Allowed output impedance
>10kOhm.

Advertisement

loading