Handling Precautions - Mitsubishi Electric A1S66ADA User Manual

Table of Contents

Advertisement

4 PROCEDURES AND SETTINGS BEFORE OPERATION

4.2 Handling Precautions

4
4 - 2
(1) Do not drop or put a great impact on the module case and the terminal block
because they are made of resin.
(2) Do not take the printed circuit board of the module out of the case. It may result in
a failure.
(3) Be careful not to let foreign matter such as filings or wire chips get inside the
module while wiring. Remove all foreign matters if any get inside.
(4) Tighten the module installation screws and terminal screws within the range as
follows :
Screw Area
Module fixing screws (M4 screw)
Terminal block terminal screws (M3.5 screw)
Terminal block installation screws (M4 screw)
(5) When loading the module to the base unit, be sure to insert the module latch to
the fixing hole, and secure the module using module mounting screw.
When removing the module, be sure to remove the module mounting screw first,
then remove the module latch from the fixing hole.
Base unit
Module fixing hole
Tightening Torque Range
Module mounting screw
Module
Module
connector
Module latch
MELSEC-A
78 to 118 N·cm
59 to 88 N·cm
78 to 118 N·cm
4 - 2