CONTENTS ..............................1 01 Device Identification 1.1 Actuator ID Label ..................................1 1.2 Legend ......................................1 ....................................... 3 02 General 2.1 Application ....................................3 2.1.1 Purpose of the Manual ..............................3 2.1.2 Qualification and Training of the Personnel ....................... 3 2.1.3 Explosive Atmosphere Zones ............................
Page 3
5.5 Position Sensing ................................... 13 5.6 Sensitivity Control ................................14 5.7 Remote Controller ................................14 5.8 Serial Communication ................................ 14 5.9 Smartrac for Asset Management ........................... 15 5.10 QR Code ....................................15 5.11 Actuator Protection ................................16 5.12 Cable Entries ..................................16 ..................................
Page 4
9.1 Alarm and Failure Messages ............................31 .............................. 31 10 Product Maintenance 10.1 General ....................................31 ....................................31 11 Service ACK21-01A ontracactuators.com...
Device Identification 1.1 Actuator ID Label Actuator: Easytrac EME/EOE Year Torque= Speed= Output flange= Signal= Pmax= Imax= Temp= IP67 Made by Ontrac line 1: actuator Type line 2: serial no. / year of construction line 3: max. switch-off torque /max. output speed...
Page 6
We remind you that the classification of the zone (REF. ATEX 2014/34/EU former 94/9/CE directive) for potentially explosive atmosphere zones has to be done by the end user and communicated to the vendor for the right choice of classification of the equipment to work in these zones.
Read the operating instructions thoroughly. All of the points presented in these instructions must be understood and observed by those persons responsible for the installation, operation, maintenance and repair of the machine. Ontrac does not accept any liability for damage resulting from failure to comply with these maintenance and operating instructions.
Safety Advice Preliminary remarks All the references to the manual have to be considered applicable also to environment and system that use these actuators unless it's specified otherwise. 2.2.1 Introduction ATTENTION: the non-observance of the indications stated in this manual or the inappropriate use of the equipment by unqualified or unauthorized staff, can cause serious personal injuries or death and damages to products and apparatus! The technical assistance office is at the complete disposal;...
2.3 Other Safety Advices: If the content of this manual conflicts with laws and regulations of local country or area, then follow relevant local and area laws and regulations. Appropriate protection is needed in some poor operating environment. All installation and commissioning work as well as electrical connection may only be carried out by trained technicians and qualified personnel.
The actuators feature protection class IP 40 when supplied. Protection class IP 67 can be guaranteed once the cable glands and the cable entries are installed. If not other specified, the Intelligent Type of Easytrac actuators are supplied with the following standard configuration: Local operate mode: ……………...
The use outside these specifications has to be agreed and approved by Ontrac. It must be considered also that, if the actuators are used outside their technical specifications, the factory warranty are no longer valid.
Main Components 4.1 Name of Each Component 1. Upper cover for motor & wiring connections compartment 2. Control panel 3. Gearcase 4. Connecting flange 5. Removable valve adaptor 6. Manual switch handle 7. Handwheel 8. Integral electrical control unit 9. Local indication 10.
Model EME50 EME100 EME200 EME400 EME600 (Intelligent Type) EOE50 EOE100 EOE200 EOE400 EOE600 Weight (Kg) 5.3 Dimensions Easytrac Basic Type Outline Dimension Drawing Direct mounting Base and lever Φ D Mode Torque Open/Close Power time Flange Weight Weight ENISO ENISO...
Page 16
Intelligent Easytrac Outline Dimension Drawing Direct mounting Base and lever Φ D Mode Torque Open/Close Power time Flange Weight Weight ENISO ENISO 5211 SP-101 5211 SP-101 EME50 Φ50 Φ49.6 50Nm 11x11 1/4-20 12Kg 16Kg EOE50 EME100 Φ70 Φ69.9 100Nm 14x14...
5.4 Key Features ● For Intelligent Model (With control unit): Password protection Auto phase correction, Phase lost detection Motor: thermo switch Input/output user programable Reverse protection Jam valve/Blockage, 1.5 torque of nominal max torque ...
5.6 Sensitivity Control Response time: Responding to control signal, to determine how fast actuator should respond to the external control commend, can choose up to 5%, rate of change, can choose with 0.5% rate of change as a step. ...
5.9 Smartrac for Asset Management Actuator setup Online simulation 5.10 QR Code For easily track factory set data and direct connect to company website for require request or operational manual download Manufacturing data authentication Service request linked to Ontrac website ACK21-01A ontracactuators.com...
5.11 Actuator Protection Easytrac provides an option for double sealing for Explosion proof, or IP68 version, for even more protection against ingress. Two seals are provided which gives additional protection when the actuator terminal compartment is open. Easytrac IP68 to mee the following requirements: •...
6.1 Actuator Check for pre-condition - Does the actuator fit to the valve? Fitting to a valve: Ontrac actuator are supplied in closed position. The units are standard configured to give clockwise output on a close command. ...
6.3 Hand Crank Force A hand crank with lever is provided for manual operation. Exceeding the permissible hand crank force, required for the max. switch-off torque, can damage the actuator and / or the valve. The following hand crank forces are required to provide the max. switch-off torque: Reduction ratio: For EOE/EME 200: 39:1, 200/39≈5Nm •...
6.5 Mounting with Base and Lever Prior to mounting, check whether there is sufficient space. Ensure that the actuator or other parts are not in the swivel range of the lever. The mounting support of the part-turn actuator muss be solid, rigid and low in vibration.
Page 24
4. Installation of Damp Rod (Provided by Customer) The following table shows the dimensions Fig.4 Selection and dimension table of ball joint Adjust parameters Inner diameter and Diameter Hinge Screw Maximum Minimum wall thickness of of direct Adjustment torque length thread adjustment adjustment...
Electrical Connection 7.1 Electrical Wiring Diagram 7.1.1 Wiring Diagrams of Intelligent Mode (with Control Unit): 3-phase AC,380V(on-off) 3-phase AC,380V(Modulating duty) 1-phase AC,220V(on-off) 1-phase AC,220V(Modulating duty) Default Setting(DI): Default Setting(DO): Function Input channel Function Output channel Open direction Full open indication Close direction Full close indication Stop direction...
3-phase AC, 380V 7.1.3 Profibus DP Wiring Diagram: Ontrac electric actuators can support Profibus- DP fieldbus protocol with additional code of "286". A Profibus network segment can connect up to 32 Ontrac electric actuators. The transmission speed of Ontrac electric actuators can be 9.6kbps ~ 1500kbps ACK21-01A ontracactuators.com...
1500 200m About 2km Baud rate Maximum number (kbps) of actuators Number of 19.2 bus type 45.45 mechanism 93.75 stations 187.5 1500 7.1.4 Modbus Wiring Diagram: Ontrac electric actuators can support Modbus protocol with additional code of "288". ACK21-01A ontracactuators.com...
5. Spring type crimping segments are used for the wiring terminals of Easytrac power line and analog / switching signal line. During operation, please insert a straight screwdriver for electrician into the hole of the wiring terminal as shown in the figure, press down the internal metal reed, then insert the bare end of the power line or signal line into the wiring hole, and loosen the screwdriver.
7.2.2 Wiring Installation of Bus Board (for option): Please use a system of personal earthing to avoid damage to the boards by electric sparks 2. Use three combination 1. Use an Allen wrench cross pan head screws to remove the Allen (M4x8) to install two L- screws on the cover in shaped stainless steel...
7.3 Anti-condensation heater Switch-on the mains supply in order to avoid condensation 7.4 Wire cross section (plug) Power cable 1.5 mm (inflexible or flexible) Signal cable 0.75 mm (inflexible or flexible) 7.5 Thread size for cable glands Metric Terminals 2xM25x1.5 Note: Please use suitable certified material in hazardous areas.
Adjustment 8.1 Mode Selector Switch Instruction The actuator is equipped with a local control panel with various elements for operation and display. Switch the mode selector switch to LOCAL in order to drive the actuator with the operating switch open/close. for parameter setting via local control panel.
8.3 Operation Menu Main Menu Structure 0.Language Set Language,English, China,Russia Set full open position 1.Adjust_O LOCAL 2.Adjust_C Set full close position STOP Device Information 3.DeviceInfo User usage level verification 4.Password REMOTE Device parameter setting 5.Setup Communication Setting 6.Communication Almost all of actuators' function can be adjusted (position setting, parameter setting, configuration, diagnosis, etc.) via control panel.
Page 33
Submenu Structure 3.1 Alarm&Failure Alarm & Failure Display 3.DeviceInfo 3.2 Information Actuator Information Default Value 5.1 Key_Mode -Local Control Mode InchingMode 5.2 DI_Mode -Digital input Control Mode InchingMode -Failure & Alarm Reset ----- 5.3 FailReset ----- -Input 4mA calibration 5.4 In4mA ----- -Input 20mA calibration 5.5 In20mA...
If required, tighten the screws. Every 2 years, check each actuator visually for leakage of oil/grease. Service • Ontrac and its partners provides comprehensive services upon request. Please visit us at www.ontracactuators.com ACK21-01A ontracactuators.com...