Tyco Central ESFR-25/WilFlow Manual
Tyco Central ESFR-25/WilFlow Manual

Tyco Central ESFR-25/WilFlow Manual

Freezer storage system

Advertisement

Quick Links

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model ESFR-25
Suppression Mode Fire Sprinkler Protection
For Storage In Refrigerated Areas
General
Description
The Model ESFR-25/WilFlow Freezer
Storage System is the outcome of a
collective technological effort between
Factory Mutual Research Corporation,
JRW Technologies, Inc., and Tyco Fire
Products. The system (Ref. Figure 1) is
intended for use in protecting high-
piled storage (e.g., palletized, solid
piled, or rack) within refrigerated ar-
eas. Without the need for a dry-pipe
system and/or in-rack sprinkler re-
quirements, the ESFR-25/WilFlow
Freezer Storage System provides
"suppression mode" versus "control
mode" fire protection, which had not
previously been available for refriger-
ated areas.
— IMPORTANT —
Tyco Fire Products requires that
installing contractors of the
ESFR-25/WilFlow Freezer Stor-
age System utilizing WilFlow
Fluid "B" be certified in proper
design, fabrication, installation,
and maintenance of the system.
Certification includes reference
to the Contractors Manual enti-
tled "Design, Installation, Fabri-
cation, and Maintenance of the
ESFR-25/Wilflow Freezer Stor-
age System Using Tyco Fire
Products
ESFR-25/WilFlow
Sprinklers" dated July 2002. Con-
tact your local Tyco Fire Prod-
ucts sales representative for
more details.
Individuals responsible for the
design, fabrication, installation,
or maintenance of the ESFR-
25/Wilflow Freezer Storage Sys-
tem utilizing WilFlow Fluid "B"
must have an overall under-
standing of the system.
Page 1 of 16
TM
/WilFlow
TM
This system utilizes Model ESFR-
25/WilFlow Early Suppression Fast
Response Sprinklers with a nominal
K-factor of 25.2 GPM/psi
LPM/bar
1/2
) in conjunction with sprin-
kler pipe that is filled with a patented
non-freezing fluid ("JRW Technolo-
gies, Inc." — WilFlow Fluid "B") that
has been specifically tested and ap-
proved for use with the Model ESFR-
25/WilFlow Sprinklers. The WilFlow
Fluid "B" remains in a liquid state to
temperatures as low as -20°F/-29°C
and is maintained at a pressure of 172
psi (11,9 bar) in the system piping
above of the Model F200 Alarm Check
Valve.
The automatic pressure maintenance
of the WilFlow Fluid "B" is accom-
plished by the use of the Maintenance
FLUID
SAMPLING VALVE
WITH OPERATING
CHAIN AND DELIVERY
TUBE
MAINTENANCE
PUMP AND TANK
FOR WILFLOW
FLUID "B"
ALARM
CHECK
VALVE
MODEL ESFR-25/WILFLOW FREEZER STORAGE SYSTEM
JULY, 2002
Tel: (215) 362-0700 / (800) 523-6512
Freezer Storage System:
1/2
(362.9
FIGURE 1
— TYPICAL SYSTEM ARRANGEMENT —
Customer Service/Sales:
Fax: (215) 362-5385
FREEZER
SPACE
ESFR-25
SPRINKLERS
VALVE
ROOM
(EXTERIOR
TO FREEZER
SPACE)
TFP314
TFP314

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Central ESFR-25/WilFlow and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco Central ESFR-25/WilFlow

  • Page 1 Inc.” — WilFlow Fluid “B”) that Factory Mutual Research Corporation, has been specifically tested and ap- JRW Technologies, Inc., and Tyco Fire proved for use with the Model ESFR- Products. The system (Ref. Figure 1) is 25/WilFlow Sprinklers. The WilFlow intended for use in protecting high- Fluid “B”...
  • Page 2: Technical Data

    TFP314 Page 2 of 16 Pump and Tank Unit (“General Air Products” — Model PLPS300-4B) lo- cated adjacent to the riser. Mainte- 9/16" (14,3 mm) nance of the WilFlow Fluid “B” at a NOMINAL MAKE-IN higher pressure than the incoming water supply helps assure that the sys- tem piping remains free of water that could compromise the effectiveness of...
  • Page 3 Page 3 of 16 TFP314 No. Description No. Description No. Description No. Description Valve Body Seat Ring Clapper Washer Spring Handhole Cover Clapper w/Bushings Self-Locking Cap Screw Handhole Cover Bolts Handhole Cover Gasket Clapper Facing Hinge Pin 3/8" NPT Plug FIGURE 3 MODEL ESFR-25/WILFLOW FREEZER STORAGE SYSTEM —...
  • Page 4 TFP314 Page 4 of 16 DESCRIPTION QTY. DESCRIPTION QTY. DESCRIPTION QTY. 300 psi/ 2000 kPa 1/4" Plug ..2 26 1/2" x 1-1/2" Water Pressure 1/2" Plug for 4 inch Nipple ... Gauge .
  • Page 5: Piping Diagram

    Page 5 of 16 TFP314 VENT LEVEL GAUGE TANK CONTROL TANK FILL TANK PANEL ISOLATION LEVEL TANK VALVE SWITCH DISCHARGE N.C. ISOLATION VALVE N.O. SUPPLY SYSTEM ISOLATION ISOLATION VALVE WITH VALVE REGENERATIVE CHECK SUPERVISORY SWITCH N.C. Y-STRAINER TURBINE PUMP VALVE N.O.
  • Page 6 TABLE B Systems” defined in NFPA 13 or ing viscous fluids. The calculation pro- HYDRAULIC DESIGN FM’s Data Sheet 2-8N do not apply gram must be the FM recognized Tyco PRESSURES and must not be utilized. Fire Products SprinkCalc Hydraulic (To protect uncartoned Program.
  • Page 7 Page 7 of 16 TFP314 Low Point Drains 1/2" BALL 1/4" MINIMUM All piping must be pitched to drain back VALVE WITH COPPER ACCUMULATOR to the riser. Low point drains shall be TEE HANDLE & TUBE SIZE installed where drainage back to the OPERATING RISER DIM.
  • Page 8 TFP314 Page 8 of 16 Such steps might include, but not be data sheet, fluid expansion can occur limited to, locating risers next to during temperature increases. As an freezer walls as opposed to the far wall option, the relief port of the Pressure of a loading dock, where feed pipe Relief Valve (Fig.
  • Page 9 Criteria with respect to pipe, system trip and eventual drain down. plication of thread sealants. Tyco threaded fittings, welding, gasketed fit- Trapping of water in this cavity will Fire Products requires the use of...
  • Page 10 TFP314 Page 10 of 16 VIEW A-A SYSTEM CONTROL VALVE (INDICATING SYSTEM ISOLATION VALVE WITH WITH SUPERVISORY SWITCH) SUPERVISORY SWITCH, N.O. MODEL F200 ALARM CHECK VALVE SUPPLY ISOLATION VALVE, N.C. SYSTEM SHUT-OFF VALVE (INDICATING TANK DISCHARGE ISOLATION WITH SUPERVISORY SWITCH) VALVE, N.O.
  • Page 11: Installation

    25/WilFlow Sprinklers are outfitted thread, truncation, etc. must be plication of thread sealants. Tyco with dielectric connections. made. Fire Products requires the use of Teflon tape or an anerobic pipe Step 8.
  • Page 12: System Setting Procedure

    TFP314 Page 12 of 16 the Pump and Tank Unit control panel Step 17. Perform an “Alarm Test” per System to the “Off” position. the alarm test procedures noted in The Care and Maintenance section. Setting NOTE Positive head pressure must be main- Step 18.
  • Page 13: Care And Maintenance

    Page 13 of 16 TFP314 other system devices, such as main ble for monitoring the installation that Care and control and shut-off valves, supervi- the fire protection system has been sory devices, sprinklers, etc. refer to returned to service. Maintenance NFPA 25 and individual manufacturers Main Drain Test instruction for information on appropri-...
  • Page 14: Service Procedures

    TFP314 Page 14 of 16 on the graph representing the tem- 1.278 perature and specific gravity readings. This point must lie within the +1% and -1% of the nominal curves shown. 1.274 Step 7. If the test results for the first sample are within the allowed toler- 1.270 ance, the inspection has been com-...
  • Page 15 Page 15 of 16 TFP314 Step 4. Open the Main Drain Valve System Isolation Valve (Fig. 8 - Item 9), that the screen protecting the drain (Fig. 8 - Item 5). opening the System Shut-off Valve restriction orifice (Fig. 4 - Item 3) has (Fig.
  • Page 16: Limited Warranty

    NESS FOR A PARTICULAR PUR- 6, or 8 Inch Model F200 Alarm Check POSE. Valve, P/N 52-201-2-049. Maintenance Pump and Tank: Specify: Model PLPS300-4B Mainte- nance Pump and Tank, P/N 54025. TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446...