Typical Field Wiring And Internal Module Wiring - DirectLOGIC DL405 Manual

Table of Contents

Advertisement

Typical Field
Shown below is a wiring diagram with typical field wiring and details relating to the
Wiring and Internal
D4–INT module's internal wiring. There are a few things you need to know before
Module Wiring
you connect the field wiring.
Module sources current if
supply is connected as
shown here.
+
+
+
Module sinks
+
current if
supply is
+
connected as
shown here.
+
These points show you how to
connect the interrupts with a single
supply. This method can only be
used if no channel-to-channel
isolation is required .
Each channel is isolated, so you can use sinking or sourcing
configurations independently for each point.
Unused inputs do not require any connections.
INTERRUPT MODULE
TB
0
4
1
5
2
6
3
7
D4–INT
10.2–26.4VDC
4–18mA
C0
C0
0
0
C1
C1
1
1
C2
C2
2
2
C3
C3
3
3
C4
C4
4
4
C5
C5
5
5
C6
6
C6
C7
6
7
C7
7
17
Derating Chart for D4–INT
Points
8
6
4
2
0
1
2
3
32
5
68
86
Ambient Temperature ( C/ F)
Current sourcing configuration shown
+V
Common
+
Optical
Input
Isolator
*
Response delay switch is set with Switch 2,
positions 5–8 on rear of the module. This is only
for points X0 – X3. Points X4 – X7 are fixed at the
fastest response.
17
17
To L
4
5
6
C
1 4
122
14
F
Response
Time Switch*
To
Circuitry