Recommended Height Of Radiant Heaters Sbc Installation - PROMIENNIKI GAZOWE SBC 2 Operating And Maintenance Manual

Ceramic radiant heaters
Table of Contents

Advertisement

CERAMIC RADIANT HEATERS

Recommended height of radiant heaters SBC installation:

NOTE: The table includes recommended values. Actual conditions may impose
exceptions from the above values.
During installation you have to pointed out minimal distance from heater to the wall in case if the
wall would not be made of refractory materials or it would not be high temperature resistance of
radiance. Minimal distance are stated in table above:
Model
SBC 2
SBC 4
SBC 6
SBC 8
SBC 10
SBC 12
SBC 16
SBC 6+6
SBC 8+8
SBC 10+10
SBC 12+12
SBC 30
NOTE: The table includes recommended values. Actual conditions may impose
exceptions from the above values.
EN.SBC_v2_1 Feb 2019
Model
SBC 2
SBC 4
SBC 6
SBC 8
SBC 10
SBC 12
SBC 16
SBC 6+6
SBC 8+8
SBC 10+10
SBC 12+12
SBC 30
Table 2.
The distance between the wall and the radiator [m]
Roof
Floor
1.5
3.0 – 3.5
1.5
3.0 – 3.5
1.5
3.0 – 3.5
1.5
3.5 – 4.5
1.5
4.0 – 5.0
1.5
4.0 – 5.0
1.5
5.0 – 6.0
1.5
4.0 – 5.0
1.5
5.0 – 6.0
1.5
5.0 – 6.0
1.5
5.0 – 6.0
1.5
7.0 – 9.0
Table 3.
Promienniki Gazowe
Height [m]
3.0 – 3.5
4.0 – 5.0
4.0 – 5.0
4.0 – 5.0
4.5 – 5.5
4.5 – 5.5
5.0 – 6.0
5.0 – 6.0
5.0 – 6.0
5.0 – 6.0
5.0 – 6.0
7.0 – 9.0
Front
Side
1.0
1.5
1.0
1.5
1.5
1.5
1.5
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
2.0
1.5
.
Sp. z o.o