Advertisement

DO NOT SEAL JOINT TRIM OR
SPLASHGUARDS TO THE FLOOR!

Plumbing

WASTE OUTLET AND P-TRAP

The waste outlet is located off the center of the case
on one side allowing drip piping to be run lengthwise
under the fi xture. There are 3 drains in each fi xture
that can be easily located.
1-1/2",1", & 3/4" P-traps and threaded adapters are
supplied with each fi xture. The 3 P-traps must be
installed to prevent air leakage and insect entrance
into the fi xture.
NOTE: PVC-DWV solvent cement is recommended.
Follow Hussmann's instructions.
INSTALLING CONDENSATE DRAIN
Poorly or improperly installed condensate drains
can se riously interfere with the operation of this
re frigerator, and result in costly maintenance and
product losses. Please follow the recommendations
listed below when installing condensate drains to
insure a proper installation:
1. Never use pipe for condensate drains smaller
than the nominal diameter of the pipe or P-trap
supplied with the case.
2. When connecting condensate drains, the P-
trap must be used as part of the condensate
drain to prevent air leakage or insect entrance.
Store plumbing sys tem fl oor drains should be at
least 14" off the center of the case to allow use
of the P-trap pipe section. Never use two water
seals in series in any one line. Double P-traps in
series will cause a lock and prevent draining.
3. Always provide as much down hill slope ("fall")
as possible; 1/8" per foot is the pre ferred
minimum. PVC pipe, when used, must be sup-
ported to maintain the 1/8" pitch and to prevent
warping.
4. Avoid long runs of condensate drains. Long
runs make it impossible to provide the "fall"
necessary for good drainage.
5. Provide a suitable air break between the fl ood
rim of the fl oor drain and outlet of condensate
drain. 1" is ideal.
6. Prevent condensate drains from freezing:
a. Do not install condensate drains in contact
with non-insulated suction lines. Suction lines
s hould be insulated with a nonabsorbent
insulation material such as Armstrong's
Armafl ex.
b. Where condensate drains are located in dead
air spaces (between refrigerators or between
a refrigerator and a wall), provide means to
prevent freezing. The water seal should be
insulated to prevent condensation.
PIPING
The refrigerant line outlets are located under the
case. Locate fi rst the electrical box, the outlets are
then on the same side of the case but at the opposite
end. Insulate suction lines to prevent condensation
drippage.
REFRIGERATION LINES
LIQUID
3/8" O.D.
NOTE: The standard coil is piped at 5/8" (suction); however, the store
tie-in may vary depending on the number of coils and the draw
the case has. Depending on the case setup, the connecting
point in the store may be
case you are hooking up.
Refrigerant lines should be sized as shown on the
refrigeration legend furnished by the store.
Install P-traps (oil traps) at the base of all suction line
vertical risers.
Pressure drop can rob the system of capacity. To keep
the pressure drop to a minimum, keep refrig erant
line run as short as possible, using the minimum
number of elbows. Where elbows are re quired, use
long radius elbows only.
10
R3(CR3),R3HV(CR3HV)-M/F-0707

Refrigeration

SUCTION
5/8" O.D.
/
",
/
", or 1
/
". Refer to the particular
5
7
1
8
8
8