Resilient Power Control Module
RPCM
Quick Install Guide
For models:
RPCM 1502 (16А)
RPCM 1532 (32А)
RPCM ME 1563 (63A - Mining Edition)
Version 201908210021

Advertisement

loading

Summary of Contents for RCNTEC RPCM Series

  • Page 1 Resilient Power Control Module RPCM Quick Install Guide For models: RPCM 1502 (16А) RPCM 1532 (32А) RPCM ME 1563 (63A - Mining Edition) Version 201908210021...
  • Page 2 Bon voyage! We hope you enjoy it! RCNTEC Team 2. Mounting onto a Rack 1. Install the cage (mounting) nuts as shown in the Fig. 1.
  • Page 3 Fig. 2. Installation of RPCM Please Note: Note. In order to prevent short-circuit protection of the terminals in the RPCM from tripping circuit breakers installed on the inputs, it is necessary to ensure complete selectivity of protection. For RPCM 1502, RPCM 1532, RPCM ME 1563, the operation current of protection against short circuit on the terminals RPCM ~ 7 to 17 iNom for 10A or from ~ 70 to ~ 170 A, the response time for short circuit is about 2 milliseconds.
  • Page 4 3. External Elements Fig. 4. Elements on the front panel of RPCM 1502 (16A) and RPCM 1532 (32A) Fig. 5. Elements on the rear panel of RPCM 1502 model (16A) Fig. 6. The difference of elements on the rear panel of RPCM 1532 (32A) Designation: 1 —...
  • Page 5: Reset To Factory Settings

    Fig. 7. The difference of elements on the front panel of RPCM ME 1563 (63A — Mining Edition) Fig. 8. The difference of elements on the rear panel of RPCM ME 1563 (63A — Mining Edition) 4. Starting to Operate Reset to Factory Settings To reset the device, hold the top button on the front panel for 20 seconds.
  • Page 6 5. Connecting via Web Interface This type of control is based on use of application level protocols: HTTP/(HTTPS). Connection is performed through an Internet browser via standard port 80. The IP address or domain name of the device registered in DNS is indicated in the browser field. For example: http://192.168.xxx.yyy is our device's IP.
  • Page 7: Connecting Via Ssh

    6. Connecting via SSH To connect via SSH protocol in UNIX-based systems, it will be sufficient to indicate from within the terminal's emulator the command: ssh ip_address. In the MS Windows environment, you can use the PUTTY program. You will need to configure settings in the Sessions section of this program.
  • Page 8: Power And Grounding Requirements

    The surface area of RPCM and slots used must be free of chips, scratches, dents, and other defects. Feedback: Contacts: http://rcntec.com/feedback http://rpcm.pro Tel: +7 (495) 009 87 87, +7 (800) 302 87 87 E-mail: info@rcntec.com...