CONFIGURATION SETTINGS
FUNCTION #3: OPERATIONAL MODES
Wireless power packs have several sequence of operation choices.
SETTING #
MODE
Automatic On Occupancy Mode
2*
3
Vacancy Mode
Partial Off Occupancy Mode
4
(Auto-On to 100% when Occupied / 50%
Dim when Unoccupied)
5
Automatic On (Disabled Off Switch)
CHANGING THE OPERATIONAL MODE
1 Read through the above list and note the number of the desired setting (e.g. 2 = Automatic On Occupancy Mode).
2 Press and release the unit's pushbutton 3 times, then wait 2 seconds. The White LED will blink back the number of the current setting (repeats 3x before exiting).
3 Interrupt blink back by pressing the button the number times equal to the new desired setting (e.g. 3 = Vacancy Mode).
4 The LED will blink back the new setting number as confirmation and will be saved after three confirmations. After the third confirmation sequence, a successful save will be indicated by
two sets of rapid White flashes. If the Blue LED rapid flashes twice, save was unsuccessful and process should be started over.
ADDITIONAL NOTES ON OPERATIONAL MODES
When in Automatic On Occupancy Mode (Setting #2) or Partial Off Occupancy Mode (Setting #4), if lights are manually switched off when there are still occupants in a
Ã
space (to show a presentation for example), the Automatic On operation will be disabled until the sensor time delay expires.
In all modes, if the switch is pressed but no occupancy is ever sensed, the lights will come on for 1 minute and then shut off. For hybrid wired/wireless power packs, if there are no
Ã
sensors wirelessly linked or wired to the unit, tie the power pack's white input wire to red (+VDC) .
When in Vacancy (Manual On) Mode (Setting #3), there is a 15 second "grace" period after the sensor times out when the sensor will switch lights back on automatically. For
Ã
dimming models, the lights will return to the previous level. After 15 seconds the sensor will revert to vacancy (manual on) operation.
FUNCTION #8: RESTORE FACTORY DEFAULTS / FORGET LINKED DEVICES
To return a wireless power pack to its original factory default settings or to clear the unit's list of linked wireless devices the following commands can be executed.
SETTING #
DESCRIPTION
3
Restore Factory Defaults
4
Restore Factory Defaults and Forget all Linked Devices
5
Enter Forget Mode (opposite of Pairing/Linking Mode
6
Forget All Linked Devices
7
Send a "Forget Me" Message
ENTERING A RESTORE FACTORY DEFAULTS OR FORGET LINKED DEVICES COMMAND
1 Read through the above list and note the number of the desired command
2 Press and release the unit's pushbutton 8 times, then wait 2 seconds. The White LED will blink back 2 times, pause and repeat.
3 Interrupt the blink back and press the pushbutton the number times equal to the desired command (e.g. 6 times to Forget all Linked Devices).
4 The LED will flash back the command number as confirmation and will be executed after three confirmations. Two sets of rapid White flashes indicates success. If the Blue LED rapid
flashes twice, the command was unsuccessful and process should be started over.
DESCRIPTION
Lights come on automatically when an occupancy signal is received from wirelessly linked sensors (and/or wired sensors on -AX models). On
dimming models the lights will turn on to the TURN ON / PARTIAL ON LEVEL as specified in Function #4. Lights will turn off automatically if
the OCCUPANCY TIME DELAY expires prior to receiving another occupied signal from a sensor. Lights can also be switched off manually if
signaled from a wirelessly linked switch (and/or wired switch on -AX models).
DEFAULT SETTING
A switch signal from a linked wireless switch (and/or a wired switch on -AX models) is required to initially turn lights on. On dimming
models the lights will turn on to the TURN ON / PARTIAL ON LEVEL as specified in Function #4. Lights will turn off automatically if the
OCCUPANCY TIME DELAY (Function #2) expires prior to receiving another occupied signal from a sensor. Lights can also be switched off
manually if signaled from a wirelessly linked switch (and/or wired switch on -AX models).
Valid on dimming models only. Lights are on at full bright (HIGH TRIM LEVEL) when wirelessly linked sensors (and/or wired sensors on -AX
models) are signaling occupancy. When unoccupied, lights are dimmed to TURN ON / PARTIAL ON LEVEL) as specified in Function #4. Note
the default value is changed to 50% when the OPERATIONAL MODE is switched to Partial Off. If a wireless switch is linked (and/or a wired
switch on -AX models), lights can be manually dropped to TURN ON / PARTIAL ON LEVEL.
Lights come on automatically when an occupancy signal is received from wirelessly linked sensors (and/or wired sensors on -AX models). On
dimming models the lights will turn on to the TURN ON / PARTIAL ON LEVEL as specified in Function #4. Lights will turn off automatically if
the OCCUPANCY TIME DELAY expires prior to receiving another occupied signal from a sensor. Lights cannot be switched off manually.
(CONT.)
Need help?
Do you have a question about the SWX-950 and is the answer not in the manual?