To Check The Water Volume And Flow Rate; Changing The Pre-Pressure Of The Expansion Vessel - Daikin Altherma EHVH04S18CB3V Installer's Reference Manual

Low temperature split
Table of Contents

Advertisement

6 Preparation
6.4.3

To check the water volume and flow rate

The indoor unit has an expansion vessel of 10 litre with a factory-set
pre-pressure of 1 bar.
To make sure that the unit operates properly:
▪ You must check the minimum and maximum water volume.
▪ You might need to adjust the pre-pressure of the expansion
vessel.
Minimum water volume
Check that the total water volume in the installation is minimum
10 litre, the internal water volume of the indoor unit NOT included.
INFORMATION
In critical processes, or in rooms with a high heat load,
extra water might be required.
NOTICE
When circulation in each space heating loop is controlled
by remotely controlled valves, it is important that the
minimum water volume is guaranteed, even if all of the
valves are closed.
a
b
c
d
f
T1
M1
e
f
FHL1
a
Outdoor unit
b
Indoor unit
c
Heat exchanger
d
Backup heater
e
Pump
f
Shut-off valve
g
Collector (field supply)
h
By-pass valve (field supply)
FHL1...3
Floor heating loop (field supply)
T1...3
Individual room thermostat (optional)
M1...3
Individual motorised valve to control loop FHL1...3 (field
supply)
Maximum water volume
Use the following graph to determine the maximum water volume for
the calculated pre-pressure.
a
2.5
2
1.5
1
0.5
0.3
0 10
50
100
150
200
a
Pre-pressure (bar)
b
Maximum water volume (l)
Example: Maximum water volume and expansion vessel pre-
pressure
Installer reference guide
26
g
h
T2
T3
M2
M3
FHL2
FHL3
b
250
300
350
400
450
Installation
height
≤280 l
(a)
difference
≤7 m
No pre-pressure
adjustment is required.
>7 m
Do the following:
▪ Increase
the
pressure.
▪ Check if the water
volume
does
exceed the maximum
allowed water volume.
(a)
This is the height difference (m) between the highest point
of the water circuit and the indoor unit. If the indoor unit is
at the highest point of the installation, the installation height
is 0 m.
Minimum flow rate
Check that the minimum flow rate (required during defrost/backup
heater operation) in the installation is guaranteed in all conditions.
NOTICE
When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating/operation).
Minimum required flow rate during defrost/backup heater
operation
04+08 models
11+16 models
See the recommended procedure as described in
during commissioning" on
page 73.
6.4.4
Changing the pre-pressure of the
expansion vessel
NOTICE
Only a licensed installer may adjust the pre-pressure of the
expansion vessel.
When changing the default pre-pressure of the expansion vessel
(1 bar) is required, take following guidelines into account:
▪ Only use dry nitrogen to set the expansion vessel pre-pressure.
▪ Inappropriate setting of the expansion vessel pre-pressure will
lead to malfunction of the system.
Changing the pre-pressure of the expansion vessel should be done
by releasing or increasing nitrogen pressure through the schräder
valve of the expansion vessel.
ERLQ004~008CA + EHVH/X04+08S18+26CB
Water volume
>280 l
Do the following:
▪ Decrease
the
pre-
pressure.
▪ Check
if
the
water
volume
does
NOT
exceed the maximum
allowed water volume.
The expansion vessel of
the indoor unit is too
pre-
small for the installation.
In this case, it is
recommended to install
NOT
an extra vessel outside
the unit.
12 l/min
15 l/min
"9.4  Checklist
Daikin Altherma – Low temperature split
4P384973-1A – 2016.02