DNP3 TCP Device Profile
1.2 DNP3 TCP Device Profile Documents
DNP3 TCP
DEVICE PROFILE DOCUMENT
Timeouts while waiting for:
Data Link Confirm
Complete Appl. Fragment
Application Confirm
Complete Appl. Response
Others:
Transmission Delay:no intentional delay
Select/Operate Timeout:configurable (default: 3 s)
Need Time Interval:fixed to 60 s
Unsolicited Notification Delay:configurable (default: 5 s)
Unsolicited Response Retry Delay:configurable (default: 10 s)
Unsolicited Response Trigger Conditions:
Number of Class 1 events: Configurable, range 1 to 1 000 (default 5)
Number of Class 2 events: Configurable, range 1 to 1 000 (default 5)
Number of Class 3 events: Configurable, range 1 to 1 000 (default 5)
Hold time after Class 1 Events: : Configurable, range 1 ms to 36 000 ms (default 5 000 ms)
Hold time after Class 2 Events: : Configurable, range 1 ms to 36 000 ms (default 5 000 ms)
Hold time after Class 3 Events: : Configurable, range 1 ms to 36 000 ms (default 5 000 ms)
Time Synchronisation:
Maximum Time Base Drift ((milliseconds per minute):
Maximum Internal Time Reference Error when set via DNP:
Maximum Delay Measurement Error:
Maximum Response Time:
Maximum Event Time-tag error:
When does outstation set IIN1.4:
14
None
Fixed at 2 s
None
Fixed at _____
None
Fixed at _____
None
Fixed at _____
- Assorted at start up until first Time Synchronisation request received
- Periodically, every 60 s
SIPROTEC Compact, Feeder Protection and Recloser Controller 7SC80, Bus Mapping/Point Lists
Variable
Configurable
Variable
Configurable
Variable
Configurable
(default: 5 s)
Variable
Configurable
10ms
10ms
10 ms
20 ms
5 ms
C53000-L2040-C353-3, Edition 09.2018