bolid S2000-IP-03 User Manual

Analog addressable rate-of-rise and fixed temperature detector
Hide thumbs Also See for S2000-IP-03:

Advertisement

Quick Links

ANALOG ADDRESSABLE
RATE-OF-RISE AND FIXED TEMPERATURE DETECTOR
IP 101-55-A1R "S2000-IP-03"
USER'S MANUAL

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the S2000-IP-03 and is the answer not in the manual?

Questions and answers

Summary of Contents for bolid S2000-IP-03

  • Page 1 ANALOG ADDRESSABLE RATE-OF-RISE AND FIXED TEMPERATURE DETECTOR IP 101-55-A1R “S2000-IP-03” USER’S MANUAL...
  • Page 2: Table Of Contents

    TABLE OF CONTENTS Description and Operation ....................5 Product Purpose ......................5 Specifications ....................... 6 Scope of Delivery......................7 Arrangement and Operation ..................7 Measuring Instruments, Tools, and Accessories ............8 Marking ........................8 Packing ........................8 Intended Use........................9 Operating Restrictions ....................
  • Page 3 This User’s Manual explains the principles of operating S2000-IP-03 Analog Addressable Rate-of-Rise and Fixed Temperature Detector of the software version 1.10. Only the personnel who have studied this manual are allowed to operation activities. All activities on mounting, programming and commissioning shall be performed in compliance with the requirements of the regulatory documentation in force at the place of operation.
  • Page 4: Description And Operation

    1 Description and Operation Product Purpose 1.1.1 S2000-IP-03 Analog Addressable Rate-of-Rise and Fixed Temperature Detector (hereinafter referred to as the detector) is to be used in fire detection and fire alarm systems to protect premises against fires by monitoring the rate of ambient temperature rise and to generate fire alarms automatically.
  • Page 5: Specifications

    Specifications Table 1.2.1 Parameter Value 1.2.1 Power supply voltage (via Polling Loop) 8 V through 11 V 1.2.2 Consumed current 0.6 mA max 1.2.3 Number of detectors within a Polling Loop 127 max 1.2.4 Maximum active resistance of polling loop wires 100 ohms max 1.2.5 Minimum insulation resistance between polling loop wires 50k ohms min...
  • Page 6: Scope Of Delivery

    MK-3 Recessed Mounting Kit* — Protection Wire Cage* — Documentation S2000-IP-03 Analog Addressable Rate-of-Rise and Fixed Temperature Detector 1pc. Operations Manual * – Supplied by separate order Arrangement and Operation 1.4.1 The detector comprises a printed circuit board, an assembled detector body, and a mounting base.
  • Page 7: Measuring Instruments, Tools, And Accessories

    − Startup: The detector has been fed from the PL controller, but no request on the detector address has yet been received. Measuring Instruments, Tools, and Accessories While mounting, commissioning, and maintaining the detector please use the instruments, tools, and accessories shown in Table 1.5.1. Table 1.5.1 Instrument Specifications...
  • Page 8: Intended Use

    Intended Use 2.1 Operating Restrictions The design of the detector doesn’t imply operating it in aggressive and dusty environments and in explosion and fire hazardous premises. Correct performance of the detector cannot be guaranteed if its electromagnetic environment does not meet the operation conditions defined in Section 1.2 of this manual. 2.2 Preparing for Use 2.2.1 Safety Measures During Preparation –...
  • Page 9 Overall dimensions are shown in Figure 2.2.2.2 (the side view) and Figure 2.2.2.3 (the bottom view). Figure 2.2.2.2 Figure 2.2.2.3...
  • Page 10: Mounting

    Mounting dimensions are shown in Figure 2.2.2.4. Figure 2.2.2.4 2.2.3 Mounting While considering mounting location for the detectors, please be guided by actual national codes and mounting rules for fire detectors - for example, by the code of practice “СП 484.1311500.2020”, in particular by the requirements shown in the table 1.
  • Page 11: Wiring

    2.2.4 Wiring Figure 2.2.4.1 shows the typical diagram for wiring the detector into the polling loop of a PL controller. The first terminal of the detector base can be used to connect a shield of the connecting wire. Figure 2.2.4.1 2.2.5 How to Open the Detector To open the detector, detach it from its base and use the blade of a flat–head screwdriver to release small clips through the rectangular hole shown in Figure 2.2.5.1.
  • Page 12: Programming The Detector

    2.2.7 Programming the Detector 2.2.7.1 Configuring The following values of Input Type are applicable for the detector: – 3: Heat Fire; – 9: Heat Analog Addressable; – 10: Thermostatic. If Input Type is selected as 3: Heat Fire, Fire Alarm messages are generated based on the internal threshold of the temperature rise rate and the threshold of maximum temperature value equal to +54°С.
  • Page 13: Operating The Detector

    2.3 Operating the Detector To be admitted to work with the detector, the personnel are obliged to have studied this manual and to have a certificate of verification of knowledge of accident prevention regulations. The detector is used along with a poling loop controller as a part of Orion ISS. To have more information about operating the system, please refer to documentation for S2000M, Orion Pro Software Suite, Sirius FACP, and the PL controller in use.
  • Page 14: Maintenance

    3 Maintenance 3.1 General The detector should be maintained under the following schedule: Table 3.1 Task Description Frequency Visual checking Six-monthly Check for operability Once a year 3.2 Safety Precautions The detector shall be maintained by persons certified with the second or higher accident prevention qualification level.
  • Page 15: Technical Examination

    Repair of faulty equipment is to be performed by the manufacturer or in authorized repair centers. The equipment shall be sent for repair in compliance with Company Standard QMS 8.5.3- 2015, which can be found online at our website https://bolid.ru/support/remont/. Attention! The equipment shall be submitted for repair being assembled and clean and along with all the parts listed in the documentation.
  • Page 16: Disposal

    24 months from the manufacturer’s date of production. Certification Information S2000-IP-03 Analog Addressable Rate-of-Rise and Fixed Temperature Detector meets the requirements of Technical Regulations of Eurasian Economic Union ‘On Requirements for Fire Safety and Fire Extinguishing Equipment’ (TR EAEU 043/2017) and is covered by the conformity certificate No.

Table of Contents