8. Installation
8.4 Indoor Unit Drain Piping
Important
The drain pipe should be at least equal in size to drain conduit of the indoor unit.
The drain pipe is thermally insulated to prevent the formation of condensation inside the pipe.
The drain up mechanism should be fitted before the indoor unit is installed and when the electricity has been
connected a little of water should be added to the drain pan and the drain pump to check and see if it is
functioning correctly.
All connections should be secure. (Special care is needed with PVC pipe)
8.4.1 Drain piping of indoor unit with drain pump
Drain piping must have down-slope (1/50 to 1/100). Be sure not to provide up-and-down slope to prevent
reversal flow.
During drain piping connection, be careful not to exert force on the drain port on the indoor unit.
The outside diameter of the drain connection on the indoor unit is 32 mm (1-1/4 inch).
– Piping material: Use the Polyvinyl chloride pipe, 25 mm (1 inch) pipe fittings.
Pipe clamp
Indoor unit
Maintenance
drain port
※ According to type of indoor unit, external appearance could be different.
Possible drain head height is upto 700 mm (27-6/19 inch). So the drain head should be installed below 700 mm
(27-6/19 inch).
Be sure to install heat insulation on the drain piping.
– Heat insulation material: Polyethylene foam with thickness more than 8 mm (5/16 inch).
Drain Pipe
※ According to type of indoor unit, external appearance could be different.
8.4.2 Drain pipe connection without drain pump
Drain piping must have down-slope (1/50 to 1/100). Be sure not to provide up-and-down slope to prevent
reversal flow.
During drain piping connection, be careful not to exert force on the drain port on the indoor unit.
The outside diameter of the drain connection on the indoor unit is 32 mm (1-1/4 inch).
– Piping material: Use the Polyvinyl chloride pipe, 25 mm (1 inch) pipe fittings.
Be sure to install heat insulation on the drain piping.
37
Indoor unit
Upward
routing
not allowed
1/50~1/100
1/50~1/100
Maximum 700mm
(27-9/16 inch)
Drain Pump
Ceiling concealed duct - Middle static pressure
Max 300mm
Metal
clamp
Insulation
※ According to type of indoor unit, external appearance could be different.
Unit
Hanger
distance
Hanger bracket
1~15m
1/50~1/100 slope
Flexible drain hose
Thermal insulation
(Local supply)
Drain pipe
(Local supply)
Elbow
Drain pump