8. Installation
8.3 Connecting pipes to the indoor unit
Refrigerant piping work
To detail information for connecting the refrigerant pipes, please refer to the installation manual included
withproduct.
Piping insulation work
Perform heat insulation work completely on both gas and the liquid pipe. Because improper insulation will result
condensate formation over pipe.
Use the heat insulation material for the refrigerant piping which has an excellent heat resistance (over 120°C
(248°F)).
Precautions in high humidity circumstance
– This air conditioner has been tested according to the "KS Conditions" and confirmed.
– If it is operated for a long time in high humid atmosphere (dew point temperature: more than 23°C(73°F)),
water drops are liable to fall. In this case, add heat insulation material according to the following procedure.
Thermal insulation for refrigerant pipe
(Local supply) Thermal insulation for
Make sure that there is no clearance here.
CAUTION
Make sure to insulate any field piping all the way to the piping connection inside the unit. Any exposed piping
may cause condensation or burns if touched.
piping(Local supply)
Overlap with
insulation
Ceiling concealed duct - Middle static pressure
• Heat insulation material : Adiabatic glass wool with
thickness of 10~20mm(13/32 ~13/16 inch).
• Stick glass wool on all air conditioners that are located
in ceiling atmosphere.