Unit Start-Up; Adding Refrigerant For Longer Line Set - Lennox 3PC036 Installation Instruction

Table of Contents

Advertisement

INDOOR WIRING DIAGRAM
Y/G
RED
Y/G
BLUE(BLACK)
YELLOW
Indoor unit
1
2 3
JX1
Outdoor unit
MAGNET
RING
To outdoor unit
PROGRAMMABLE
WIRED
CONTROLLER
Note1:COMPONENT IN
DASH LINE IS OPTIONAL
OR FIELD WIRING.
Note2:The programmable
wired controller and CCM
COMM.BUS use the same
port CN42 CN41

Unit Start-Up

IMPORTANT
Units should be energized 24 hours before unit start-up
to prevent compressor damage as a result of slugging.
1. Inspect all factory- and field-installed wiring for loose
connections.
2. Verify that the manifold gauge set is connected.
3. Add additional refrigerant charge if required before
opening valves and while system is still under a
vacuum.
4. Open the liquid and suction line service valves to
release the refrigerant charge contained in outdoor
unit into the system.
5. Replace the stem caps and tighten to the value listed
in "Table 1. Torque Requirements" on page 8.
6. Check voltage supply at the outdoor unit terminal strip.
The voltage must be within the range listed on the
unit's nameplate. If not, do not start the equipment
DC FAN
MOTOR
P_1
L-OUT
Input:230VAC
(or 115VAC)
L-IN(or CN 2)
N-IN
Input:230VAC
(or 115VAC)
Output:
CN31
CN32
12VDC
Output:0-24VDC
2
Input:12VDC
CN43
MULTI-FUNCTION CONTROL BOARD
Output:
12VDC
CN42 CN41
Output:
X Y E 5V/12V
CN45
5VDC
CCM
COMM. BUS
ALARM
FOR SETTING NETADDRESS (CCM Comm.Bus)
ENC3+F1
(MULTI-FUNCTION
CONTROL BOARD)
CODE
NETADDRESS
FACTORY SETTING
Figure 28. 3WMC036 Indoor Unit Wiring Diagram
HORIZONTAL
M
SWING MOTOR M
5
CN12
Output:310VDC
(or 140VDC)
MAIN CONTROL BOARD
Output:
CN18
5VDC
MAGNET
Input:
4(8)
RING
5VDC
CN1
CN40
Output:
3
Input:
5VDC
5VDC
Output:
0-5VDC
CN46
CN4
ROOM TEMP.
SENSOR(T1)
REMOTE
ON/OFF
0
0
ON
1 2
8
8
0~F
0~F
16~31
0~15
until you have consulted with the power company and
the voltage condition has been corrected.
7. Refer to the included user guide to operate the system
using the provided remote control.
8. Visually check for binding of both indoor and outdoor
fans.

Adding Refrigerant for Longer Line Set

The outdoor unit is factory-charged with refrigerant.
Calculate the additional refrigerant required according to
the diameter and the length of the liquid pipe between the
outdoor unit and indoor unit connections.
Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
Maximum line set length is 213 feet (65 meters).
Table 8. Additional Refrigerant Charge
System Size
(KBtu)
36
18
M
5(10)
Output:
CN19
12VDC
Output:
5
12VDC
CN22
CN15
Output:
INDOOR COIL
0-5VDC
OUTLET
TEMP. SENSOR(T2)
DISPLAY BOARD
4
Output:
CN3
5VDC
Output:
5
CN2
5VDC
Output:
5VDC
CN21
CN5
OCCUPANCY
5(4or 3)
5
HUMIDITY SENSOR
0
ON
ON
1 2
1 2
8
0~F
32~47
Pipe Length
Amount of Refrigerant
(feet / meters)
>25 (7.5)
0.322 oz/ft (30g/m)
M
VERTICAL
SWING MOTOR
WiFi
MODULE
WIRED
CONTROLLER
SENSOR
0
ON
1 2
8
0~F
48~63
to add