› (See chap “chapter name”): this entry indicates another section in the Manual that you should refer to. › Device: this term is used referring to the boiler. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 5
PRODUCT CONFORMITY RADIANT BRUCIATORI spa declares that its gas boilers comply with the European Directives and with the requirements provided in the European standards below: › Eco-design Directive 2009/125 CE, R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
1. INSTALLER SECTION 1. INSTALLER SECTION The installation operations described in this section should be performed only by qualified personnel, having the appropriate technical training in the field for the installation and maintenance of components of civil and industrial domestic hot water production and heating plants.
1.1.3. REFERENCE LEGISLATION The installation must be realized according to the requirements of current legislation and in compliance with local technical regulations, according to the indications of the good technique. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
› Turn the boiler at 90° holding it with your hand (fig. 1-B). › Lift the box (fig. 1-C) and remove the guards (fig. 1-D). fig. 1 R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
H - 1000 mm X - 60 mm fig.1 It is allowed an outdoor installation in a partially protected location (i.e. shelter, balcony) that respect the minimum measure indicated in figure 1200 mm R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 13
R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
(see fig.1) so as to allow the condense to drain. fig.1 1.1.8. CIRCULATOR PREVALENCE/ FLOW DIAGRAM Wilo-Yonos PARA MSL 12/6B p/kPa Q/m³/ h Q/l/s Q/Igpm max. Q/m³/ h Appliance Loss R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
The company assumes no liability for damage caused to persons or for failure to comply with these instructions. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
“M” (fig. 2) to make sure that the system pressure reaches 1.2 bar (fig. fig. 2 after performing this operation, make sure that the loading tap “R” (fig. 2) is properly closed. fig. 3 R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
› Connect the dedicated flexible condensate draining tube “P” to a waste disposal system. The condensate can be drained directly in the sewerage system by inserting an easily serviceable siphon. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
If the temperature goes below -10° centigrades, please fill the plant with anti-freeze liquid (CLEANPASS FLUIDO AG cod. 98716LA) and insert and electrical resistances kit (cod. 82259LP). R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
› the gas supply pressure falls within the values It is strictly forbidden the use of adaptors, indicated on the data plate. multiple plugs and/or extensions for the general power supply of the equipment from the electrical network. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
M0904 and then connect the two non-polarized conductors of the environment Thermostat or Remote control (see ‘TA’ or ‘CR’ fig. 2). After performing these operations, remount the crankcase and the front casing. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
› Make sure that the discharge tube doe not protrude inside the fumes exhaust duct, stop before it reaches the inner surface of the latter. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
The ducts must be certified for this specific use and for a temperature greater than 100 °C. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 23
The locations in which are installed gas devices must be vented so as to ensure the amount of air necessary for a regular combustion and for location ventilation. The natural air intake must take place directly through: R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Subsequent addition of a curve is similar to adding a linear length of tube according to the indications below: co-axial curve Ø80/125 at 90° = 0.8 m co-axial curve Ø80/125 at 45° = 0.5 m R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 25
Subsequent addition of a curve is similar to adding a linear length of tube according to the indications below: curve Ø80 at 90°= 1.5 m curve Ø80 at 45°= 1.2 m R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 26
Subsequent addition of a curve is similar to adding a linear length of tube according to the indications Ø125 below: Ø 80 curve Ø80/125 at 90° = 0.8 m curve Ø80/125 at 45° = 0.5 m Ø 100 R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
1. SUPPORT CENTRE SECTION 2. SUPPORT CENTRE SECTION All operations described below relative to first start- up, maintenance and replacement should be performed only by qualified personnel and authorized by RADIANT BRUCIATORI S.p.A.
Local and National Laws and Standards; › make sure that the heating system gate valves are open; › make sure that there is no intake of gaseous products within the system; R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
› If the flame is missing, the board will repeat the start-up operations after post-ventilation (20 seconds). › You might have to repeat the start-up operation several times to release all the air inside the gas R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
2 › After each adjustment variation on screw ‘1’ (fig. 2) of the gas flow adjuster you have to wait R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
'P00' to appear on the display, then release the buttons. Use the keys ‘ ’ and ‘ ’ of the heating circuit to select the parameter to be edited. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 32
’ and ‘ ’ buttons of the domestic circuit to change the parameter value. Keep the ' ' button pressed until the parameter is displayed in order to confirm the modified value. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 33
2. FIRST START-UP To quit the parameters menu, press the ' button until 'OFF' is displayed. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
THE BOILER ACTIVITY IN CASE OF HIGH HEATING FLOW FOR FLOOR SYSTEMS TEMPERATURE. THE COMPANY ASSUMES NO LIABILITY FOR DAMAGE CAUSED TO PERSONS OR FOR FAILURE TO COMPLY WITH THESE INSTRUCTIONS. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 35
THROUGH THIS PARAMETER YOU CAN SET THE PUMP IN MULTIPLES OF 5 OPERATION DURATION ON THE DOMESTIC CIRCUIT, AFTER SECONDS THE TAP IS CLOSED. (PRE-SET AT 24 X 5 = 120 SECONDS) R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 36
IN HEATING MODE [SEE CHAPTER ‘HEAT CAPACITY DIAGRAM (KW) –ELECTRIC FAN FREQUENCY (HZ)’]. THE VALUE IS PRE-SET BASED ON THE SET POWER (SEE PARAMETER P00) AND ON THE GAS TYPE (SEE PARAMETER P02) R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 37
SUCH DOMESTICH HOT WATER TREATMENT (AND INFORM THE USERS) TO AVOID UNFORSEEABLE DAMAGES TO PERSONS, ANIMALS AND PROPERTY. A THERMOSTATIC VALVE SHOULD BE INSTALLED AT THE DOMESTIC HOT WATER OUTLET TO AVOID ANY BURNS. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 38
(ONLY WITH MODULATING PUMP AND RETURN PROBE CONNECTED) IN PERCENTAGE THROUGH THIS PARAMETER YOU CAN SET THE MINIMUM SPEED VALUE OF THE MODULATING PUMP DURING A REQUEST TO OPERATE IN HEATING MODE. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 39
STARTING VALUE OF THE STORAGE TANK, COMPARED TO THE USER ADJUSTABLE D.H.W SETPOINT. TYPE OF VISUALIZATION 00 - 01 00 = HEATING CIRCUIT TEMPERATURE ONLY 01 = TEMPERATURE ACCORDING TO THE TYPE OF OPERATION (D.H.W. OR HEATING) R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
2. FIRST START-UP 2.1.6. ELECTRIC FAN FREQUENCY/HEAT CAPACITY DIAGRAM FREQUENCY (Hz) GAS TYPE MINIMUM FREQUENCY MAXIMUM FREQUENCY R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
› remove and clean the burner from oxidation; or neutralization devices for acid condensate. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 42
2. MAINTENANCE › check that the liquid flow is not obstructed and that there are no combustion gas refluxes inside the internal system. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Domestic circuit Adjustable domestic temperature °C 35-60 Maximum pressure for domestic circuit Minimum pressure for domestic circuit Specific capacity in continuous service - Δt 30°C litres/min Dimensional characteristics Width Depth R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 44
D.H.W Min. fan speed - G30 Fuel consumption - G30 kg/h 2,68 Nominal Supply pressure - G31 mbar Heating Max. fan speed - G31 D.H.W Max fan speed - G31 R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 45
For boiler space heaters and boiler combination heaters: 88,3 At 30 % of rated heat output and low-temperature regime 97,7 At rated heat output of cogeneration space heater with CHP100+Sup0 R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 46
(*) High-temperature regime means 60 °C return temperature at heater inlet and 80 °C feed temperature at heater outlet. (**) Low temperature means for condensing boilers 30 °C, for low-temperature boilers 37 °C and for other heaters 50 °C return temperature (at heater inlet). R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
11. SAFETY THERMOSTAT 12. HEATING PROBE 13. EXPANSION TANK 14. ELECTRIC FAN 15. WATER PRESSURE SWITCH 16. MODULATING PUMP 17. GAS VALVE 18. FLOW SWITCH 19. SAFETY VALVE 3 bar R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
› remove the fastening screws (2 - fig.1) placed on the front edge of the side panel; › grab the bottom of the panel and remove it by moving it sideways and then pulling it upwards (see fig. 1). R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
› unscrew the two fastening screws 1 - fig. 1; › disengage the four hooks ‘2’ - fig. 1; fig. 1 › remove the crankcase pulling it upwards. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
› close the main supply tap of the water supply network; › open all cold and hot water taps; › after completing all operations, close the discharge tap and all previously opened water taps. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
EQUAL TO THE ONE MEASURED BETWEEN PHASE AND GROUND, YOU HAVE TO INSTALL A PHASE-PHASE TRANSFORMER KIT (COD. 88021LA) SAFETY THERMOSTAT THERMOSTAT CABLE CHECK THE WIRING: AUTOMATIC. (95°C) DISCONNECTED; BROKEN THERMOSTAT. REPLACE IT. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 54
CHECK THE WIRING. PROBE CONNECTOR. RETURN PROBE BROKEN OR INCORRECTLY REPLACE IT; AUTOMATIC. CALIBRATED PROBE (RESISTANCE VALUE 10 KOHM AT 25 °C NTC); DISCONNECTED OR WET CHECK THE WIRING. PROBE CONNECTOR. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 55
SUPPLY VOLTAGE FALLS BACK WITHIN THE REQUESTED LIMITS). GENERAL INTERNAL INCORRECT SIGNAL IF THE MODULATION BOARD DOES NOT AUTOMATIC. BOARD ERROR RECOGNITION BY THE RESET THE ERROR AUTOMATICALLY, MODULATION BOARD REPLACE IT. MICRO-PROCESSOR. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
YOU CAN ACTIVATE/DEACTIVATED IT BY HOLDING SIMULTANEOUSLY AND FOR 7 SECONDS ‘ ’ THE RESET ‘ ’ AND OF THE HEATING CIRCUIT . THE “FAST H2O” FUNCTION GUARANTEES THE IMMEDIATE D.H.W SUPPLY AT THE REQUESTED TEMPERATURE. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
‘GAS TYPE SELECTION’ from the control panel fig. 3 (see chapters ‘MIAB3013 PARAMETERS TABLE’ and ‘ACCESSING AND PROGRAMMING THE PARAMETERS’); › adjust the CO2 combustion value as indicated in chapter ‘CO2 VALUE CHECK AND CALIBRATION’. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
1. USER SECTION 3. USER SECTION The operations described in this section are addressed to all those who will use the machine. The machine must be used and accessed only by qualified operators that fully read and understood the User section, paying particular attention to the warnings.
To validate the warranty, the boiler must create an air exchange that can quickly clean be started by a technical Support Centre authorized the location; by RADIANT no later than 30 days from the date of installation. › Close the gas valves; WARNING ›...
3. USE 3.1.2. CONTROL PANEL DOMESTIC WATER TEMPERATURE ADJUSTMENT KEYS OPERATING MODE SELECTION KEY: SUMMER / HEATING ONLY / WINTER / OFF RESET KEY: ANOMALY RESET HEATING TEMPERATURE ADJUSTMENT KEYS DISPLAY R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
INDICATION OF PARAMETER NUMBER OR DISPLAYED INFO CODE. FLAME PRESENT SIGNALLING. ERROR DISPLAY THAT CAN BE RESET. OPERATION IN HEATING MODE ENABLED. fig. 1 PARAMETERS PROGRAMMING FUNCTION ACTIVE. OPERATION IN DOMESTIC MODE ENABLED. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
LIST OF DISPLAYED DATA INFO CODE ICON DESCRIPTION DOMESTIC CIRCUIT PROBE TEMPERATURE HEATING CIRCUIT TEMPERATURE BURNER ACTUAL OUTPUT POWER (EXPRESSED IN PERCENTAGE) RETURN PROBE TEMPERATURE EXTERNAL PROBE TEMPERATURE FAN SPEED FREQUENCY R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
OFF MODE burner; this is indicated by displaying the symbol ‘ ’ blinking. In this mode the boiler no longer meets the heating and domestic hot water demands, the anti-freeze, R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
› the boiler is not blocked. › Or leave the boiler in OFF operating mode keeping active the electrical and gas supplies so that the anti-freeze function may activate. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
2 minutes system relief cycle. Throughout this function the display will fig. 1 show the code “F33”. The boiler can work normally only after completing the operation. fig. 2 R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
IT, AS SOON AS THE ERROR CODE DISAPPEARS, THE BOILER WILL RESTART AUTOMATICALLY. IF THE BLOCK PERSISTS CONTACT THE TECHNICAL SUPPORT CENTRE. REMOTE CONTROLLER INCOMPATIBLE CONTACT THE TECHNICAL SUPPORT CENTRE. SUPPLY VOLTAGE CONTACT THE TECHNICAL SUPPORT CENTRE. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
Page 68
CUT OFF THE POWER SUPPLY FROM THE MAIN SWITCH AND THEN RESTORE IT, AS SOON AS THE ERROR CODE DISAPPEARS, THE BOILER WILL RESTART AUTOMATICALLY. IF THE BLOCK PERSISTS CONTACT THE TECHNICAL SUPPORT CENTRE. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
› the hot water is immediately supplied at the requested temperature. › unnecessary delays are avoided by increasing the comfort of the final user. › water wastes are limited waiting that the water reaches the right temperature. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...
(Waste Electrical and Electronic Equipment) shows that this product can not be dismantled as domestic waste. Proper dismantle of this product helps preventing potentially negative consequences on human health and environment. R1KR 34 - RAD - ING - Manual - 1807.1_SK.2_MIAB3013_R7_PDX...