Safety Instructions
If user's mounting orientation is not according to the recommended mounting orientations,
please consult Delta for further information.
To ensure sufficient convection cooling, always maintain a safety distance of ≥ 50 mm (1.97
inch) from all ventilated surfaces while the device is in operation.
The device is not recommended to be placed on low thermal conductive surface.
For example, plastics.
For safety reason, please ensure the mounted device is kept at 8 ≥ mm safety distance for
D1 from other components and equipment (Refer to Fig. 2.)
The enclosure of the device can become very hot depending on the ambient temperature
and load of the power supply. Do not touch the device while it is in operation or
immediately after power is turned OFF. Risk of burning!
Do not touch the terminals while power is being supplied. Risk of electric shock.
Prevent any foreign metal, particles or conductors from entering the device through the
openings during installation. It may cause: Electric shock; Safety Hazard; Fire; Product
failure
The power supply must be mounted by metal screws onto a grounded metal surface. It is
highly recommended that the Earth terminal on the connector be connected to the
grounded surface.
2.
Device Descriptions
Refer to Fig. 1.:
1
Input & Output terminal block connector
2
DC voltage adjustment potentiometer
3
DC OK control LED (Green)
3.
Installation of the Device
A
Base Mounting: Fig. 3 show the mounting hole locations for power supply assembly
onto a metal mounting surface. Fig. 5, only use M4 screw ≤ 3 mm (0.20 inch) through
the base mounting holes. This is to keep a safe distance between the screw and
internal components.
B
Fig. 3: Connector
C
Fig. 3: This surface belongs to customer's end system or panel where the device is
mounted.
Use flexible cable (stranded or solid) of AWG 18-12. User should calculate and select the
suitable wire specification (type/quantity/diameter) according to actual output current. The
torque at the Connector shall not exceed 8 Kgf.cm. (6.94 lbf.in). The insulation stripping
length should not exceed 0.275" or 7 mm. (Refer to Fig. 4).
Recommended mounting tightening torque: 4~7 Kgf.cm (3.47~6.08 lbf.in).
REV.00
PMR-☐V320W1AT (Terminal Block)
Fig. 1. Device Descriptions
Base Mounting (Horizontal)
Fig. 3. Recommended Mounting Orientations & Mounting Hole Locations
Stripped wire
Lug
Fig. 4. Wire Type
PMR-☐V320W1AT
D1 ≥ 8 mm
Fig. 2. Assembly Reference
Fig. 5. Assembly Reference
www.DeltaPSU.com

Advertisement

loading

Summary of Contents for Delta PMR V320W1AT Series

  • Page 1 PMR-☐V320W1AT (Terminal Block) • If user’s mounting orientation is not according to the recommended mounting orientations, please consult Delta for further information. • To ensure sufficient convection cooling, always maintain a safety distance of ≥ 50 mm (1.97 inch) from all ventilated surfaces while the device is in operation.
  • Page 2 PMR-☐V320W1AT 使用說明書 使用说明书 安全規範 安全规范 • • 若欲使用非建議的安裝方式時,敬請諮詢台達。 若欲使用非建议的安装方式时,敬请咨询台达。 與通風表面保持至少 50mm 的距離,以確保對流冷卻充分。 与通风表面保持至少 50mm 的距离,以确保对流冷却充分。 • • • 本產品不適合擺放在低熱導體,例如:塑膠。 • 本产品不适合摆放在低热导体,例如:塑胶。 由 於 安 全 考 量 , 請 確 保 安 裝 的 設 備 保 持 在 8 ≥ mm 的 安 全 距 離 D1 由...

This manual is also suitable for:

Pmr-24v320w1atPmr-48v320w1atPmr-12v320w1at