Read Only Status Parameters - S&S Northern ODE-3-110023-101 Setup Manual

Table of Contents

Advertisement

17

Read Only Status Parameters

Read Only Status Parameters - P00.xx
The Optidrive E3 has a number of read only status parameters which can be used for monitoring and an aid to
fault finding within the system.
The read only parameters are accessed through parameter P-00.
Set P-14 to 101 to access P00-01 to P00-30 or P-14 to 201 to access P00-01 to P00-50.
Go to P-00 and press the Navigate button, P00-01 will be shown on the display.
The table below shows the most useful read only status parameters. Please see the E3 User Guide for a full list
of the read only status parameters.
Parameter
Description
P00-01
Analogue input 1 value (%)
P00-02
Analogue input 2 value (%)
P00-03
Speed ref input (Hz/RPM)
P00-04
Digital input status
P00-05
PI controller output (%)
P00-06
DC bus voltage ripple (VDC)
P00-07
Applied motor voltage (VAC)
P00-08
DC Bus voltage (VDC)
P00-09
Heatsink temperature (
P00-10
Run
manufacture
P00-13
Trip log
P00-20
Internal drive temperature
P00-26
kWh/MWh meters
P00-28
Software version & checksum
P00-29
Drive type identifier
P00-30
Drive serial number
P00-32
Actual switching frequency
P00-01 & P00-02 – Analogue input 1 & 2 value
P00-01 & P00-02 display the value of the analogue inputs (terminal 4 and 6) as a percentage of the input.
0 to 10V: 0V = 0%, 10V = 100%
4 to 20mA: 4mA = 0%, 20mA = 100%
0 to 20mA: 0mA = 0%, 20mA = 100%
P00-03 – Pre-ramp reference
P00-03 displays the speed reference before the acceleration or deceleration ramps are applied to it. The
speed reference maybe from an analogue input or preset speed etc.
P a g e
| 50
o
C)
time
since
date
of
Optidrive E3 Set-up Guide
Explanation
0 to 10V / 4 to 20mA = 0 to 100%
0 to 10V / 4 to 20mA = 0 to 100%
Pre-ramp speed reference in Hz or RPM if P-10>0
Displays the status of the digital inputs
Displays the output of the PI controller (0 to 100%)
Measured DC bus voltage ripple
Displays the RMS voltage being applied to the motor
Displays the drives internal DC bus voltage
Displays the drives internal heatsink temperature
Displays the run time since date of manufacture.
parameter is not affected by setting factory defaults.
Displays the 4 most recent trips with time stamp
Internal drive ambient temperature in
Displays the kWh and MWh consumed by the drive
Displays the drives control processor and power stage
processor software versions and checksum
Displays the drive rating, frame size, voltage output phases
Displays the drives unique 11 digit serial number
Displays the drives actual switching frequency (See P00-09)
This
o
C.

Hide quick links: