Start Mode & Auto Restart - S&S Northern ODE-3-110023-101 Setup Manual

Table of Contents

Advertisement

Start Mode & Auto Restart
The start mode on Optidrive E3 can be configured by the user as follows using parameter P-30:
Start Mode
Following a power on or keypad reset, the drive will not start if digital input 1
E E E E D D D D G G G G E E E E ~ ~ ~ ~ R R R R
(terminal) remains closed. The input must be opened and then closed after a power
(Default)
on or keypad reset to allow the drive to run.
Following a power on or keypad reset, the drive will automatically run if digital input
A A A A U U U U T T T T o o o o ~ ~ ~ ~ 0 0 0 0
1 (terminal 2) is closed.
Auto restart – see description below
A A A A U U U U T T T T o o o o ~ ~ ~ ~ 1 1 1 1
to
A A A A U U U U T T T T o o o o ~ ~ ~ ~ 5 5 5 5
Terminal Reset
Digital input 1 (terminal 2) is used as a RESET terminal when parameter P-15 is set to modes 0, 1, 2, 3, 4, 6, 8,
14, 15, 16, 17 & 18.
Digital input 1 (terminal 2) or Digital input 2 (terminal 3) is used as a RESET terminal when parameter P-15 is
set to modes 5, 7 & 9.
To reset the drive in momentary control when P-15 is set to 10, 11 or 13, the normally closed (NC) STOP
terminal must be toggled (opened and closed) and then the drive will run when the normally open (NO) run
pushbutton is pressed.
NOTE: If the drive is set up in with P-15 in any mode apart from the momentary modes (P-15 = 10, 11 or 13)
and P-30 is set to
E E E E D D D D G G G G E E E E ~ ~ ~ ~ R R R R
or
reset the drive, as soon as digital input 1 or 2 is opened and then closed, the drive will enable and run.
Auto Restart
If parameter P-30 is set to
A A A A U U U U T T T T o o o o ~ ~ ~ ~ 1 1 1 1
In addition, following a trip, the drive will make up to 5 attempts to restart at 20 seconds intervals. The
number of restart attempts are counted and if the drive fails to start on the final attempt, the drive will trip
with a fault code on the display and will require the user to manually reset the fault. The drive must be
powered down to reset the Auto restart counter.
NOTE: Parameter 30 contains another 2 indexes (parameters). These parameters are associated with Fire
Mode. If fire mode is not being used, these 2 indexes can be ignored.
A A A A U U U U T T T T o o o o ~ ~ ~ ~ 0 0 0 0
mode, if the drive trips and digital input 1 or digital input 2 is used to
to
A A A A U U U U T T T T o o o o ~ ~ ~ ~ 5 5 5 5
the drive will operate and reset the same as if
Optidrive E3 Set-up Guide
13
Start Mode & Auto Restart
Description
A A A A U U U U T T T T o o o o ~ ~ ~ ~ 0 0 0 0
was set.