Section 4. Setting the Unit

4.1 Pad Installation
When installing the unit on a support pad, such
as a concrete slab, consider the following:
• The pad should be at least 1" larger than the
unit on all sides.
• The pad must be separate from any structure.
• The pad must be level.
• The pad should be high enough above grade
to allow for drainage.
• The pad location must comply with National,
State, and Local codes.

Section 5. Refrigerant Line Considerations

5.1 Refrigerant Line and Service Valve Connection Sizes
5.2 Factory Charge
The outdoor condensing units are factory
charged with the system charge required for the
outdoor condensing unit, ten (10) feet of tested
connecting line, and the smallest rated indoor
evaporative coil match. Always verify proper
system charge via subcooling (TXV/EEV) or
superheat (fixed orifice) per the unit nameplate.
6
Line Sizes
Vapor
Model
Line
A4AC6036B
3/4
A4AC6037B
3/4
A4AC6042B
7/8
A4AC6060B
1-1/8
A4AC6018A
3/4
A4AC6024A
3/4
A4AC6030A
3/4
A4AC6031A
3/4
A4AC6036A
3/4
A4AC6037A
7/8
A4AC6042A
7/8
A4AC6048A
7/8
A4AC6060A
7/8
Table 5.1
Service Valve Connection Sizes
Liquid
Vapor Line
Line
Connection
3/8
3/4
3/8
3/4
3/8
7/8
3/8
3/4
3/8
3/4
3/8
3/4
3/8
3/4
3/8
3/4
3/8
3/4
3/8
3/4
3/8
7/8
3/8
7/8
3/8
7/8
LINE TYPE
Suction
Liquid
Line
Line
3/4"
3/8"
7/8"
3/8"
Liquid Line
Connection
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
3/8
TUBING INFORMATION
REFRIGERANT TO ADD AT SPECIFIED
ADDITIONAL LENGTH
20 ft
30 ft
40 ft
50 ft
3 oz
9 oz
15 oz
21 oz
3 oz
9 oz
16 oz
22 oz
88-A4AC6001-1F-EN
60 ft
27 oz
28 oz