Section 18. Pressure Curves

520
470
420
370
(4)
320
270
220
170
50
170
165
160
155
150
145
140
135
130
125
120
115
50
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EXAMPLE: (1) OUTDOOR TEMP. 82 F.
(2) INDOOR WET BULB 67 F.
(3) AT INTERSECTION
(4) LIQUID PRESSURE @ 600 CFM IS 310 PSIG
(5) SUCTION PRESSURE @ 600 CFM IS 141 PSIG
30
PRESSURE CURVES (Refer below table for models)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
(3)
60
70
80
OUTDOOR TEMPERATURE (Degree F)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM
71, 67, 63 AND 59 DEG F.
(5)
60
70
80
OUTDOOR TEMPERATURE (Degree F)
(1)
90
100
110
(3)
(1)
90
100
110
ACTUAL:
LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
(2)
OD Model
120
A4AC6036B1
A4AC6037B1
A4AC6042B1
71
(2)
67
63
59
120
88-A4AC6001-1F-EN
Cooling
@SCFM
1000
950
1250