Toshiba Carrier RAV-SM122BTP-UL Installation Manual page 29

Hide thumbs Also See for Carrier RAV-SM122BTP-UL:
Table of Contents

Advertisement

Wired
Wireless remote controller
remote
Sensor block display of
controller
receiving unit
display
Main defective parts
Operation Timer
Indication
Ready
Flashing
GR GR OR
F12
ALT
TS sensor error
F13
ALT
Heat sink sensor error
Temp. sensor
F15
ALT
connection error
Indoor unit, other
F29
SIM
P.C. board error
F31
SIM
Outdoor unit P.C. board Outdoor
Outdoor unit
compressor
H01
breakdown
Outdoor unit
H02
compressor lock
Outdoor unit current
H03
detect circuit error
Case thermostat
H04
operation (1)
Outdoor unit
H06
low-pressure system
error
Duplicated header
L03
SIM
indoor units
Group line in individual
L07
SIM
indoor unit
Indoor group address
L08
SIM
not set
Indoor unit capacity
L09
SIM
not set
L10
SIM
Outdoor unit P.C. board Outdoor
LAN communication
L20
SIM
error
Other outdoor unit
L29
SIM
error
Abnormal external
L30
SIM
input into indoor unit
(interlock)
Phase sequence
L31
SIM
error, etc.
55-EN
Judging
Parts to be checked / error description
conditioner
device
TS sensor may be displaced, disconnected or
Outdoor
Entire stop
short-circuited.
Abnormal temperature was detected by the temp.
Outdoor
Entire stop
sensor of the IGBT heat sink.
Temp. sensor (TE/TS) may be connected
Outdoor
Entire stop
incorrectly.
Indoor
Indoor P.C. board --- EEPROM error
Auto-reset
Outdoor P.C. board ---- In the case of EEPROM
Entire stop
error.
Current detect circuit, power voltage --- Minimum
frequency was reached in the current releasing
Outdoor
Entire stop
control or short-circuit current (Idc) after direct
excitation was detected
Compressor circuit --- Compressor lock was
Outdoor
Entire stop
detected.
Current detect circuit, outdoor unit P.C. board ---
Outdoor
Abnormal current was detected in AC-CT or a
Entire stop
phase loss was detected.
Outdoor
Malfunction of the case thermostat
Entire stop
Current, high-pressure switch circuit, outdoor P.C.
Outdoor
board --- Pressure sensor error was detected or
Entire stop
low-pressure protective operation was activated.
Indoor address setting error --- There are two or
Indoor
Entire stop
more header units in the group.
Indoor address setting error --- There is at least
Indoor
one group-connected indoor unit among individual
Entire stop
indoor units.
Indoor address setting error --- Indoor address
Indoor
Entire stop
group has not been set.
Indoor
Indoor unit capacity has not been set.
Entire stop
In the case of outdoor P.C. board jumper wire
Entire stop
(for service) setting error
Network
Address setting, central control remote controller,
adapter
network adapter --- Duplication of address in
Auto-reset
central
central control communication
control
Other outdoor unit error
Entire stop
1) Communication error between IPDU MCU and
Outdoor
CDB MCU
Entire stop
2) Abnormal temperature was detected by the heat
sink temp. sensor in IGBT.
External devices, outdoor unit P.C. board ---
Indoor
Abnormal stop due to incorrect external input into
Entire stop
CN80
Operation
Power supply phase sequence, outdoor unit P.C.
continued
Outdoor
board --- Abnormal phase sequence of the 3-phase
(thermost
power supply
at OFF)
Wired
Wireless remote controller
remote
Sensor block display of
controller
Air
receiving unit
display
status
Operation Timer
Indication
Ready
Flashing
GR GR OR
P01
ALT
P03
ALT
P04
ALT
P05
ALT
P07
ALT
P10
ALT
P12
ALT
P15
ALT
P19
ALT
P20
ALT
P22
ALT
P26
ALT
P29
ALT
P31
ALT
: Lighting
: Flashing
: OFF
ALT : When two LEDs are flashing, they flash alternately. SIM : When two LEDs are flashing, they flash in synchronization.
Receiving unit display OR : Orange GR : Green
– 28 –
Judging
Main defective parts
Parts to be checked / error description
device
Indoor fan motor, indoor P.C. board --- Indoor AC
Indoor unit fan error
Indoor
fan error (fan motor thermal relay activated) was
detected.
Outdoor unit discharge
An error was detected in the discharge temp.
Outdoor
temp. error
releasing control.
Outdoor unit
High-pressure switch --- The IOL was activated
high-pressure system
Outdoor
or an error was detected in the high-pressure
error
releasing control using the TE.
The power wire may be connected incorrectly.
Open phase detected
Outdoor
Check open phase and voltages of the power
supply.
Abnormal temperature was detected by the temp.
Heat sink overheat
Outdoor
sensor of the IGBT heat sink.
Drain pipe, clogging of drainage, float switch
Indoor unit water
Indoor
circuit, indoor P.C. board --- Drainage is out of
overflow detected
order or the float switch was activated.
Abnormal operation of the indoor fan motor, indoor
The fan error of the
Indoor
P.C. board, or indoor DC fan (over current or lock,
indoor unit
etc.) is detected.
There may be gas leakage from the pipe or
Gas leakage detected
Outdoor
connecting part. Check for gas leakage.
4-way valve, indoor temp. sensors (TC/TCJ) --- An
Outdoor
4-way valve error
error was detected due to temperature drop of the
(Indoor)
indoor unit heat exchanger sensor when heating.
High-pressure
Outdoor
High-pressure protection
protective operation
Outdoor unit fan motor, outdoor unit P.C. board ---
Outdoor unit fan error
Outdoor
An error (overcurrent, locking, etc.) was detected in
the outdoor unit fan drive circuit.
IGBT, outdoor unit P.C. board, inverter wiring,
Outdoor unit inverter
compressor --- Short-circuit protection for
Outdoor
Idc activated
compressor drive circuit devices (G-Tr/IGBT) was
activated.
Outdoor unit position
Outdoor unit P.C. board, high-pressure switch ---
Outdoor
error
Compressor motor position error was detected.
Another indoor unit in the group is raising an alarm. Entire stop
Other indoor unit error
Indoor
E03/L07/L03/L08 alarm check locations and error
description
: The air conditioner automatically enters the auto-address setting mode.
Air
conditioner
status
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Entire stop
Auto-reset
Entire stop
Entire stop
Entire stop
Entire stop
Auto-reset
EN
56-EN