Applicable Controls - Toshiba Carrier RAV-SM122BTP-UL Installation Manual

Hide thumbs Also See for Carrier RAV-SM122BTP-UL:
Table of Contents

Advertisement

9

Applicable controls

REQUIREMENT
It takes some time before the remote control
becomes operable when the remote control is used
for the first time. This is not a malfunction.
<When the power is turned on for the first time
after installation>
It takes about 5 minutes before the remote
control becomes operable.
About 5 minutes
Remote
control
" "
Power on
" " flashes
becomes
disappears
operable.
<When the power is turned on from the
second time>
It takes about 1 minute before the remote
control becomes operable.
About 1 minute
Remote
" "
control
Power on
" " flashes
disappears
becomes
operable.
• Normal settings were made when the indoor unit
was shipped from factory.
Change the indoor unit settings as required.
• Use the wired remote controller to change the
settings.
* The settings cannot be changed using
the wireless remote controller, sub remote
controller, or remote-controller-less system
(for central remote controller only). Therefore,
install the wired remote controller to change the
settings.
Item
1. Test mode
Settings for when performing the test operation after installation
Registration of information about the contact number for service, model name and
2. Register service info
serial number of the indoor unit and outdoor unit
3. Alarm history
List of latest 10 alarm data: information of check code, date, time, and unit
Monitoring data of sensor temperature, rotating speed of the compressor or other
4. Monitor function
factor.
5. Setting louver position
Change the louver indication setting to match the indoor unit type.
Set whether or not the operation mode can be selected when setting the schedule
6. Setting timer operation mode
timer.
7. DN setting
Advanced settings using DN code
39-EN
Basic procedure for changing
settings
Change the settings while the air conditioner is not
working. (Stop the air conditioner before making
settings.)
CAUTION
Set only the CODE No. shown in the following table:
Do NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible
to operate the air conditioner or other trouble with
the product may result.
 Field setting menu
1
Push the [
MENU] button to display the
menu screen.
Push and hold the [
MENU] button and
the [
˅ ] button at the same time to
display the "Field setting menu".
Push and hold the buttons for more than 4
seconds.
Push the [
CANCEL] button to return.
Function
 DN setting
Perform the advanced settings for the air conditioner.
Carry out the setting operation while the indoor unit
is stopped. (Turn off the air conditioning unit before
starting the setting operation.)
2
Push the [
˄ ] / [
˅ ] button to select
"7. DN setting" on the "Field setting menu"
screen, then push the "
[
F2] button.
The fan and louver of the indoor unit operate.
When the group control is used, the fan and
louver of the selected indoor unit operate.
3
Move the cursor to select "Code(DN)" with the
"
˂ " [
F1] button, then set
"Code(DN)" with the [
˄ ] / [
4
Move the cursor to select "Data" with the
"
>" [
F2] button, then set "Data"
with the [
˄ ] / [
˅] button.
5
Push the [
MENU] button to set the other
Code (DN) and Data. After "Continue?" is
displayed on the screen, push the
"
Yes" [
F1] button.
6
Push the "
No" [
F2] button to
finish the setting operation. "
Setting"
appears on the screen for a while, then the
screen returns to the "Field setting menu"
screen.
 Pushing the "
No" [
displays the unit selection screen when the
group control is used. Push the [
button on the unit selection screen to finish the
setting operation. "
Setting" appears on the
screen for a while, then the screen returns to the
"Field setting menu" screen.
– 20 –
 External static pressure
settings
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure
1
2
3
4
5
6
(
).
Set"
• Specify [5d] to the CODE No. in procedure
• For the SET DATA of procedure
DATA of the external static pressure to be set up
from the following table.
SET DATA
External static pressure
SM122 to SM242
0000
0.12 in.WG
(Factory default)
0001
0.26 in.WG
0002
0.20 in.WG
0003
0.40 in.WG
0004
0.32 in.WG
0005
0.48 in.WG
˅ ]button.
0006
0.60 in.WG
SET DATA
External static pressure
SM302 to SM482
0000
0.20 in.WG
(Factory default)
0001
0.12 in.WG
0002
0.40 in.WG
0003
0.60 in.WG
0004
0.48 in.WG
0005
0.68 in.WG
0006
0.80 in.WG
F2] button
CANCEL]
3
.
4
, select a SET
EN
40-EN