Mounting the EchoPod
The sensor should always be mounted perpendicular to the liquid surface using the
®
provided Viton
mounting gasket. Insure that there are no restrictions or obstacles in
the path of the ultrasonic signal. Further mounting information can be found on the
Flowline website at www.flowline.com.
Mounting with a Tank Adapter: Select a tank adapter fitting, such as the LM52-
2890.
Mounting with a Riser: As installations with tall, narrow risers can impede the
acoustic signal. 2" diameter risers should be no taller than 4". Larger diameter risers
should be no taller than 12".
Mounting with a Side Mount Bracket: Use Flowline's LM50-1001 side mount
bracket.
Riser Mounting
We do Your Level Best
Side Mounting
Using the drop-down menus on the left of the WebCal screen, set the configuration
for your application requirements. When a selection does not apply to your
application, "Not Applicable" will appear in the drop-down. Make sure all drop-downs
are set appropriately for your application before moving to the Tank Level section.
NOTE: If you would like to start over, click the
Clear Screen button on the right.
Enter the appropriate tank level set points for your application.
Units. Display measurements in inches
or centimeters.
Sensor Height. Distance measured from
the bottom of the empty tank to the
bottom of the transducer. Under factory
configuration, this becomes the 4 mA set
point.
Fill Height. Distance measured from the
bottom of the empty tank to the maximum
fill height within the tank. Under factory
configuration, this becomes the 20 mA
set point.
Relay Set Points. Distance measured
from the bottom of the empty tank to each
relay set point.
Tank Level Settings