Download Print this page

Clevertronics L10 LIFELIGHT PRO LLIFE-PRO-SMC Series Installation & Maintenance Instructions

Surface mount emergency

Advertisement

Quick Links

Clevertest and Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
Zoneworks and DATA Monitored Options
Luminaires with part numbers
-ZW, -DATA
(nodes).These fittings are monitored using either Powerline Carrier Technology that utilises the power
cable to provide data communication or a dedicated data cable to/from data routers installed on a
dedicated data trunk connected to a central Server (can also be connected via Ethernet/Internet/Fibre).
Zoneworks software on the server is used to monitor, coordinate testing and collate test data from each
Lifelight. Zoneworks LLIFEs can be commissioned by a single push of the test switch or scanning of the
supplied barcode. The LED Test Switch indicator provides a multifunction indication of the status of the
Lifelight during testing and normal operation:
State
LED Operation
Commissioned
LED on Solid (Green)
Un-commissioned
LED flashes at 0.5Hz (0.5s Green, 0.5s Yellow)
Emergency Light Test In Progress
LED flashes at 3s On (Yellow) & 0.5s Off
In the case of the DATA version a 2-way "figure 8" cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)
DALI EM Option
Luminaires with part numbers
-DALI
are fitted with DALI modules (nodes) that facilitate connection and
integration to 3
rd
Party Lighting Control Systems. Before installing the -DALI please confirm that the
Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -DALI will be
addressed and configured into the control system by the Lighting Control System Commissioning
Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
"IDENTIFY COMMAND"
Fitting goes into emergency mode for 10 seconds
A 2-way "figure 8" cable and terminal block facilitates the connection to the DALI network OR a 5/6way
"structured wiring system" lead and plug facilitating the power and DALI connection. DALI connections
are marked as Da Da.
.
are fitted with Zoneworks communications modules
L10™ LIFELIGHT PRO Surface Mount Emergency
Installation & Maintenance Instruction Leaflet
Designed
in
Australia
to
comply
requirements of AS2293.3: 2005 and AS CISPR15:
2017.
NOTE: Standard product codes with this symbol
enabled with Clevertest Plus capability. Please refer to
the operation guide supplied with the product for details.
Models:
LLIFE-PRO-SMC-xx-yy
Testing
:
Manual Test
xx = Blank
Zoneworks
xx = ZW
Zoneworks DATA
xx = DATA
DALI Registered
xx = DALI
Clevertest
xx = CT (NOTE: Products supplied with the Clevertest Plus Symbol
are activated with Clevertest PLUS capability. Please refer to the
operation guide supplied with the product for details).
Spare Parts:
1530230
BATTERY: L10 3.3V 5AH. 200mm lead. Brkt.
1100819
Lifelight Pro Head Assembly, Round, LT, Gen 2
1100817
Lifelight Pro Head Assembly, Round, LT, Blk, Gen 2
LLIFE-PRO-CKIT-NP
LifelightPro, Control Only, L10, NP
AUM01270250102
LLIFE-PRO-SMC-CKIT-DALI-NP, LifelightPro, Control Only, SMC, Dali
Reg, LP, NP
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.\
Victoria (Head Office & Manufacturing)
Website:
www.clevertronics.com.au
Email:
info@clevertronics.com.au
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
New South Wales
Phone: +61 2 8805 6400
Fax: +61 2 8805 6444
Queensland
with
the
Phone: +61 7 3442 9700
Fax: +61 7 3442 9777
South Australia/Northern Territory
Phone: +61 8 8301 8800
are
Fax: +61 8 8351 8286
Western Australia
Phone: +61 8 9248 3720
Fax: +61 8 9248 3725
New Zealand
Phone:+64 800 548 448
:
Options
Black
yy = BLK
1941010
V2.1
3 March 2020

Advertisement

loading
Need help?

Need help?

Do you have a question about the L10 LIFELIGHT PRO LLIFE-PRO-SMC Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Clevertronics L10 LIFELIGHT PRO LLIFE-PRO-SMC Series

  • Page 1 Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -DALI will be Testing Options addressed and configured into the control system by the Lighting Control System Commissioning Technicians and not Clevertronics. Manual Test xx = Blank Black...
  • Page 2 IEC 60598-2-22 testing environment. Excessive battery cycling will reduce through-life performance and may lead to premature battery failure. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED from Clevertronics warranty terms. Warranty: For Product Warranty information and Terms and Conditions of Sales please refer to our website http://clevertronics.com.au/terms-conditions-sale-australia-nz/...