Clevertest and Clevertest Plus
Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
Zoneworks, HIVE and DATA Monitored Options
Fittings with part numbers
-ZW, -HV/-HVG, -DATA
(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power
cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated
data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can
also be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor,
coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by
a single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator
provides a multifunction indication of the status of the fitting during testing and normal operation:
Option
State
ZW, HV, HVG,
Commissioned
DATA
ZW, DATA
Un-commissioned
Un-commissioned
HV, HVG
With network connectivity
Un-commissioned
HV, HVG
Without network connectivity
Emergency Light Test In
ZW, DATA
Progress
Emergency Light Test In
HV, HVG
Progress
In the case of the DATA version a 2-way "figure 8" cable and terminal block facilitates the connection
to the DATA network via a multi-drop bus (daisy chain connection). For further information of
installation of a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning
Guide (incl. DATA version)
DALI EM Option
Luminaires with part numbers having
-DALI
are fitted with DALI modules (nodes) that facilitate connection
and integration to 3
rd
Party Lighting Control Systems. Before installing the -DALI luminaire, please confirm
that the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -DALI
fitting will be addressed and configured into the control system by the Lighting Control System
Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
"IDENTIFY COMMAND"
Lamp and Status LED Flash for 30 seconds
A 2-way "figure 8" cable and terminal block facilitates the connection to the DALI network. DALI
connections are marked as Da Da.
are fitted with Zoneworks communications modules
LED Operation
LED on Solid (Green)
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
Batt plugged-in: yellow 250mS,
green 250mS, yellow 250mS, green
250mS, green 1s
Batt unplugged: red 250mS, off
250mS, red 250mS,off 250mS, off 1s
LED flashes at yellow 5s , 0ff 1s
LED flashes at yellow 1s , 0ff 1s
L10™ LIFELIGHT PRO Surface Mount
Emergency
Installation & Maintenance Instruction Leaflet
Designed in Australia to comply with the requirements
of AS2293.3: 2005 and AS CISPR15: 2017.
NOTE: Standard product codes with this symbol
enabled with Clevertest Plus capability. Please refer to the
operation guide supplied with the product for details.
Models:
LLIFE-PRO-SMC-xx-yy
Testing
:
Manual Test
xx = Blank
Zoneworks
xx = ZW
Zoneworks DATA
xx = DATA
DALI Registered
xx = DALI
HIVE
xx = HV/HVG
Clevertest
xx = CT (NOTE: Products supplied with the Clevertest Plus Symbol
are activated with Clevertest PLUS capability. Please refer to the
operation guide supplied with the product for details).
Spare Parts:
1530230
Replacement Battery
1100869
Replacement Emergency LED
1100872
Replacement Emergency LED
AUM01370210001
Replacement Emergency Driver
Important:
It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.
Victoria (Head Office & Manufacturing)
Website:
www.clevertronics.com.au
Email:
info@clevertronics.com.au
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
New South Wales
Phone: +61 2 8805 6400
Fax: +61 2 8805 6444
Queensland
Phone: +61 7 3442 9700
Fax: +61 7 3442 9777
South Australia/Northern Territory
Phone: +61 8 8301 8800
Fax: +61 8 8351 8286
are
Western Australia
Phone: +61 8 9207 0000
Fax: +61 8 9207 0088
New Zealand
Phone: +64 800 548 448
:
Options
Black
yy = BLK
(-BLK)
1942306
V1.4
20 May 2022
Need help?
Do you have a question about the L10 LIFELIGHT PRO LLIFE-PRO-SMC Series and is the answer not in the manual?
Questions and answers