Adjustment Elements - Siemens FCM2018-U3 Series Mounting & Installation

Operating unit
Table of Contents

Advertisement

LED
Color
H53
Yellow
H54
Red
H61
Yellow
H842
Green

1.5 Adjustment elements

Siemens Industry, Inc.
Building Technologies Division
Function
Condition
'CPLD fail' (reset and
Off
watchdog logic)
On
Off
'TEMP', CPU module
excess temperature
On
indicator
'SPEED', Ethernet
Off
transmission indicator
On
'LINK' control indicator
Off
On
S32: Reset key
The 'S32' button has a number of functions depending on how long it is pressed for
and whether it is pressed in combination with other buttons.
Operation
Press for <2 s
Press for >2 s
Press S32 + 'Reset' or
'Acknowledge' (front operating
buttons) at the same time
Restore factory settings
Operation
Press S32 + 'Reset' (front
operating button) for > 2 s at
the same time
You will find the detailed instructions in the following documents:
A6V10315021 for Desigo
A6V10333434 for Cerberus PRO
Updating the firmware
Operation
Press S32 + 'Acknowledge'
(front operating button) for
> 2 s at the same time
firealarmresources.com
Meaning
Normal operation
Logic unit failed; replace component or contact hotline
Normal operation
CPU >45 °C
Data transfer at 10 Mbit/s
Data transfer at 100 Mbit/s
No Ethernet connection
Ethernet connection established
Function
Panel is shut down and restarted in a controlled manner. This
procedure takes up to five minutes.
Panel is shut down and restarted immediately. This may lead
to data loss. This procedure takes up to two minutes.
Restore factory settings or update firmware.
Function
Panel is started in Restore factory settings mode.
A short peeping sound confirms the function is being executed.
Function
Panel's firmware is updated.
A short peeping sound confirms the function is being executed.
Operating unit FCM20xx
Adjustment elements
A6V10315030_b_en_--
2013-06-04
1
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcm2019-u3 seriesFcm2035-u series