Indicators - Siemens FCM2018-U3 Series Mounting & Installation

Operating unit
Table of Contents

Advertisement

1
Operating unit FCM20xx

Indicators

Element
Position
Plug connections
Indicators
Switch, keys
1.4 Indicators
LED
Color
H37
Yellow
H38
Yellow
H39
Yellow
H50
Yellow
H51
Red
H52
Yellow
10
Siemens Industry, Inc.
Building Technologies Division
Des.
Function
1
Shield plate
2
Space for key switch (T45)
X3
Connection for periphery board or fire terminal board (supply and data
signals)
X5
Ethernet connection
X11
N.C.
X12
N.C.
X13
Slot for network module (SAFEDLINK) FN2001
X14
Slot for RS485 class A module (isolated) FCA2016
X15
Not used
X19
Slot for RS485 class A module (isolated) FCA2016
X400
Connection for peripheral data bus
H37 ... H61
LED indicators
H842
H841
Buzzer
S32
Reset key
S33
Switch for ground fault supervision of the Ethernet connection
S37
Support for license key
S38
Switch for ground fault supervision of the system supply
Function
Condition
Diagnosis 1
Off
On
Diagnosis 2
Diagnosis 3
'MSP fail' (processor
Off
periphery)
On
'PD ready', installation
Off
ready to switch off
On
'PPC fail' (CPU
Off
module)
On
firealarmresources.com
Meaning
Normal operation
Ground fault present
Not used
Not used
Normal operation
Processor in degraded mode; replace component or
contact hotline
Installation in operation
Installation may be disconnected from the mains
Normal operation
Processor in degraded mode; replace component or
contact hotline
A6V10315030_b_en_--
2013-06-04