Accessories; Outdoor Temperature Sensor Kit - Bd710487302V - ECR International Dunkirk DCB-75 Installation, Operation & Maintenance Manual

Condensing wall mounted gas fired boiler
Table of Contents

Advertisement

1. 1K Ohm (1k Ω) Outdoor Temperature
Sensor Kit - BD710487302V
• Use the Outdoor Sensor (OAS) Kit with Heating Only
or Combi Boilers.
• Wire Control to boiler M2 terminal strip, terminals 4 and
5 as shown.
• Install/locate Control follow supplied instructions with
sensor kit and Installation, Operation and Maintenance
Manual (IOM).
Setting "Kt" Climate Curve:
1.
Boiler automatically recognizes OAS sensor when wired to
M2 terminal block. Display changes to show current default
"Kt" value (80). Note display value.
2.
When operating in CH mode, boiler setpoint is determined
by the Kt value selected and actual outside air
temperature. Refer to applicable °F (or °C) chart, (pg. 30)
for setpoint information.
• Select Kt range which will satisfy the desired boiler
delivery temperature based on outdoor temperature
range expected for your location. For example: if you
need 176°F water when the outside temperature is 20°F
and colder, select 35 for your Kt setting.
• To change"default" Kt value on boiler control use
CH Heating buttons.
• Restrict the upper limit of the Kt curve by using Parameter
P16 to set the maximum boiler water temperature. P16
Default is 176°F.
3.
When OAS is installed, pressing
no longer display boiler CH setpoint temperature. It now
displays the Kt value which can range from 10 to 90.
4.
When scrolling has stopped, boiler will automatically
"SAVE" value as new Kt default value and automatically
return to CH mode when no Kt adjustment activity
is sensed. Kt values can be changed in +/- 1 point
increments.
5.
To return, to verify or change current Kt "default value,
depress one of the CH setpoint adjustment buttons (once),
or
, while in any heating or standby mode. Adjust
Kt value to obtain desired comfort level.
For temperatures below -40°F (-40°C), maximum heating flow temperature set point no longer
increases and curves on the graph become horizontal. Boiler set point will override sensor
Note
setpoint.

ACCESSORIES

or
buttons will
Flow Temp
°C
80 Is Default.
1k Ω
Boiler Control Panel
or
Display
Outside Temp
30
Operating
(CH)
Mode
Heating Water
Adjustments
°F
PN 240011430 REV. Q [03/15/2022]