Modbus registers

For a detailed description of specific functions please refer to the product documentation
CE1Z4634
Reg.
Process Values
1
2
3
256
Parameters
257
258
259
260
261
262
513
514
515
516
764
765
766
767
768
769
6 / 14
Siemens
Smart Infrastructure
1)
.
Name
R/W
Setpoint
RW
Override control
RW
Actual position
R
Command
RW
Opening direction
RW
Adaptive Mode
RW
Operating Mode
RW
MinPosition
RW
MaxPosition
RW
Actuator Running Time
R
Backup Mode
RW
Backup Position
RW
Backup Timeout
RW
Startup Setpoint
RW
Modbus Address
RW
Baudrate
RW
Transmission Format
RW
Bus Termination
RW
Bus Conf. Command
RW
Status
R
Unit
Scaling
Range / enumeration
%
0.01
0..100
--
--
0 = Off / 1 = Open / 2 = Close
3 = Stop / 4 = GoToMin / 5 = GoToMax
%
0.01
0..100
--
0 = Ready / 1 = Adaption / 2 = Selftest
3 = ReInitDevice / 4 = RemoteFactory
Reset
--
--
0 = CW / 1 = CCW
--
--
0 = Off / 1 = On
--
--
1 = POS
%
0.01
0..100
%
0.01
0..100
s
1
150
--
--
0 = Go to BackupPosition
1 = Keep last position
2 = Disabled
%
0.01
0..100
s
1
0..65535
%
0.01
0..100
--
--
1..247 / 255 = "unassigned"
0 = auto / 1 = 9600 / 2 = 19200
--
--
3 = 38400 / 4 = 57600 / 5 = 76800
6 = 115200
--
--
0 = 1-8-E-1 / 1 = 1-8-O-1
2 = 1-8-N-1 / 3 = 1-8-N-2
--
--
0 = Off / 1 = On
--
--
0 = Ready / 1 = Load / 2 = Discard
--
--
See below
A6V10881143_en--_d