Installation

Table 2. Static pressure drop through accessories
(inch W.G.) — standard air handler
Unit Model
Tons
Number
TWE0604*A/B
5
6
TWE0724*B
TWE0904*A/B
7.5
TWE1204*A/B
10
12.5
TWE1504*B
15
TWE1804*B
20
TWE2404*B
25
TWE3004*B
Installation for 5-10 Ton Air
Handlers
1. Refer to parts list for corresponding unit model and
correct part number/quantity.
2. Locate kit label and place next to an open spot near
the nameplate. See
Figure 1, p.
3. From
Figure 1, p.
4, loosen the two screws on
panel. Set panel aside.
4
2" MERV 13
CFM
FILTER
1600
0.22
2000
0.29
2400
0.36
1920
0.15
2400
0.19
2880
0.24
2400
0.19
3000
0.25
3600
0.31
3200
0.19
4000
0.25
4800
0.31
4000
0.15
5000
0.20
6000
0.25
4800
0.19
6000
0.25
7200
0.31
6400
0.22
8000
0.29
9600
0.36
8000
0.29
100-
00
0.37
120-
00
0.47
4.
Figure 1. Panel removal and label location
4. Remove original air filters. See
Figure 2. Remove filter
5. Locate two filter racks and loosen four screws on
filter rack.
Figure 3, p.
Figure 2, p.
4.
5.
ACC-SVN218B-EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Odyssey bayfilt002Odyssey bayfilt003Odyssey bayfilt004Odyssey bayfilt005Twe051Twe060 ... Show all