3. Charge Performance Curve
Fig.2-2 is the battery voltage vs charge time curves at 25° C
4. Internal resistance and short circuit current
The internal resistance of the battery is a dynamic nonlinear parameter that is
continuously changed along with the temperature and discharge state. The internal
resistance is the lowest when battery is fully charged. The table 2-4 shows the internal
resistance and short circuit current of Narada battery in fully charged state according
to the IEC60896-21/22 standard.
Table 2-4. Internal resistance and short circuit current (25° C)
Type
12NDT26
12NDF50
12NDF85
12NDF100
12NDF125
12NDF155
Operation manual for Acme series V4.2
Fig.2-2. Charge Curves at 25° C
Internal resistance (mΩ)
10.3
8.87
6.47
6.31
5.70
4.27
- 15 -
Short circuit current (A)
1218
1407
1864
1979
2229
2906