Advertisement

Not More Than Three Conductors in Raceway or Cable or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)
Size
60°C
(140°F)
AWG
TYPES
RUW, T
MCM
TW, UF
6
55
4
70
3
80
2
1
0
00
000
0000
250
300
350
400
500
Ambient
For ambient temperatures over 30°C, multiply the ampacities shown by the appropriate correction factor to deter-
Temperature
mine the maximum allowable load current.
°C
31-40
.82
41-50
.58
51-60
......
61-70
......
71-80
......
+ The load current rating and the overcurrent protection for these conductors shall not exceed 15 amperes for 14 AWG. 20 amperes for 12 AWG.
and 30 amperes for 10 AWG copper; or 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum and copper-clad aluminum.
* For dry locations only. See 75°C column for wet locations.
KW
Number Of
Input
Elements
6
9
12
3
13.5
15
18
18
24
27
6
30
36
36
40.5
9
45
54
Amperage Table/Over-current Protection
The tables above provides the total connected heating element
load in amperes for branch circuit conductor and over-current
protection sizing. Single-phase heaters are two wire circuits. Three-
phase heaters are three wire circuits. In addition to the foregoing, a
grounded conductor is required.
The rating of the over-current protection must be computed on
the basis of 125% of the total connected load amperage. Where
Table 3. Allowable Ampacities of Insulated Conductors
75°C
85°C
(167°F)
(185°F)
TYPES
FEPW
RH, RHW
RUH,
TYPES
THW,
V, MI
THWN,
XHHW
USE, ZW
COPPER
65
70
85
90
100
105
115
120
130
140
150
155
175
185
200
210
230
235
255
270
285
300
310
325
335
360
380
405
.88
.90
.75
.80
.58
.67
.35
.52
......
.30
Element
Single Phase
wattage
208V
240V
2000
29
25
3000
44
38
4000
58
50
4500
65
57
5000
73
63
6000
- - -
75
3000
87
- - -
4000
116
100
4500
130
113
5000
145
125
6000
- - -
150
4000
173
- - -
4500
195
169
5000
217
188
6000
- - -
225
Temperature Rating of Conductor
90°C
60°C
(194°F)
(140°F)
TYPES
TA, TBS
SA, AVB
TYPES
SIS, =FEP,
RUW, T
=FEPB,
TW, UF
=RHH,
=THHN,
=XHHW*
70
40
90
55
105
65
120
75
140
155
185
210
235
270
300
325
360
405
CORRECTION FACTORS
.91
.82
.82
.58
.71
......
.58
......
.41
......
Table 4. Standard kW Inputs
Full Load Current In Amperes
277V
480V
208V
22
13
17
33
19
25
44
25
34
49
29
38
55
32
42
65
38
- - -
- - -
- - -
50
87
50
67
98
57
75
109
63
84
130
75
- - -
- - -
- - -
100
147
85
113
163
94
125
195
113
150
the standard ratings and settings do not correspond with this
computation, the next higher standard rating or setting should be
selected.
Heater Circuits - Electronic Control Models
The water heater's electrical components are pictured and identified
in Figure 1 (page 8) and Figure 2 (page 9). The model and
rating plate illustration on page 4 identifies heater circuit ratings. The
electronic control model has two electrical circuits:
75°C
85°C
(167°F)
(185°F)
TYPES
RH, RHW
RUH
TYPES
THW,
V, MI
THWN
XHHW,
USE
ALUMINUM OR COPPER-CLAD ALUMINUM
50
55
65
70
75
80
90
95
100
110
120
125
135
145
155
165
180
185
205
215
230
240
250
260
270
290
310
330
.88
.90
.75
.80
.58
.67
.35
.52
......
.30
Number ot
Three Phase
240V
480V
Thermostats
15
8
22
11
29
15
33
17
37
18
44
22
- - -
- - -
58
29
65
33
73
37
87
44
- - -
- - -
98
49
109
55
130
65
Commercial Electric Water Heaters • 15
Installing the Water Heater
Size
90°C
(194°F)
TYPES
TA, TBS,
SA, AVB
AWG
SIS,
=RHH,
MCM
=THHN,
=XHHW*
55
6
70
4
80
3
95
2
110
1
125
0
145
00
165
000
185
0000
215
250
240
300
260
350
290
400
330
500
Ambient
Temperature
°F
.91
86 –104
.82
105–122
.71
123–141
.58
142–158
.41
159–176
Number of
Fuses
3
6
6
12
9
18