10

Test run

Before test run
Before turning on the power supply, carry out the
following procedure.
1) By using insulation tester (500VMΩ), check
that resistance of 1MΩ or more exists between
the terminal block L to N and the earth
(grounding).
If resistance of less than 1MΩ is detected, do
not run the unit.
2) Check the valve of the outdoor unit being
opened fully.
To protect the compressor at activation time, leave
power-ON for 12 hours or more before operating.
Before starting a test run, set addresses by following
the Installation Manual supplied with the outdoor
unit.
◆ Requirements for turning
thermostat OFF
Cooling operation
When the outdoor/suction air temperature is lower
than or equal to 19 °C.
When the outdoor/suction air temperature is lower
than or equal to 3 °C above the set temperature.
Heating operation
When the outdoor/suction air temperature is lower
than or equal to -10 °C
When the outdoor/suction air temperature is higher
than or equal to 15 °C.
When the outdoor/suction air temperature is higher
than or equal to 3 °C above the set temperature.
45-EN
Execute a test run
When a fan operation is to be performed for an
individual indoor unit, turn off the power, short circuit
CN72 on the circuit board, and then turn the power
back on. (Set the operation mode to "fan" to operate
the unit.) When the test run has been performed
using this method, be sure to release the short
circuit of CN72 after the test run is completed.
Operate the unit with the remote controller as usual.
For the procedure of the operation, refer to the
attached Owner's Manual to the outdoor unit.
A forced test run can be executed in the following
procedure even if the operation stops by
thermostat-OFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
CAUTION
Do not use the forced test run for cases other than
the test run because it applies an excessive load to
the devices.
– 23 –
Wired remote controller
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
1
Push and hold OFF timer button and
[ ] setting button simultaneously for
10 seconds or more. [TEST] is displayed
on the display part and the test run is
permitted.
2
Push ON/OFF button.
3
Push menu button to select the
operation mode. Select [
Cool] or
[
Heat] with [ ] [ ] setting button,
and then push menu button (three times)
again to determine the operation mode.
Do not run the air conditioner in a mode other
than [Cool] or [Heat].
The temperature setting function does
notwork during test run.
The check code is displayed as usual.
4
After the test run, push OFF timer button
to stop a test run.
([TEST] disappears on the display and the air
conditioner enters the normal stop mode.)
46-EN