2.8 Control Loop Terminal Function Table

Category Terminal
Number
FWD
REV
X3
Multi-
functional
X4
Digital
Input
X5
Terminal
X6
X7
Y1
Y2
Digital
Output
Terminal
DO
AI1
Analog
Input/
Output
Terminal
AI2
Functional Specification of Control Loop Terminal
Functions
Effective when short circuit between(FWD、
REV、X3、X4、X5、X6、X7) ~ COM, and the
functions are set by parameters F7.00 ~ F7.06
(common port: COM)
X7 can work as one of the multi-functional
terminals, also as high-speed pulse input
terminal with programming, see F7.06.
Multi-functional programmable collector open
circuit output channel 2, can be programmed
as DO terminal of various functions (common
port: COM)
Can be programmed as impulse output
terminal of various functions as many as 13
kinds (common port: COM). See F6.23.
All receives voltage/current input. Jumper JP3
(for jumper terminal All) can select voltage or
current input mode, and voltage input is the
default one. For current input, just short the
middle and another pin with the jumper cap.
AI 2 only receives voltage input. Measuring
range setting is function code F6.00 ~ F6.11.
(reference ground: GND)
Specification
INPUT, 0 ~ 24V level
signal, low level effective,
5mA.
OUTPUT, maximum load
current ≤ 50mA.
OUTPUT, output
frequency range
F6.32 ~ F6.35, set
maximum frequency as
high as 50KHz.
INPUT, input voltage
range: 0 ~ 10V (input
impedance: 100KΩ), input
current range 0 ~ 20mA
(input impedance: 500Ω).