SAFE Addressing - Inserting / Deleting Devices
CAN ONLY BE CARRIED OUT USING COMMSTOOL SOFTWARE & PC
If removing
device(s) -
remove the SAFE
address(s)
STOP THE LOOP
WIRE IN NEW DEVICE
or REMOVE DEVICE
RE-ALLOCATE
LOOP
NOTE MAP/DEVICE
CONFLICT
If Adding
device(s) - SAFE
Address them
CHECK
LOOP MAP
*
For Main Loop/mid-spur insertion follow the instruction.
For insertion on a Spur End connection,
select the t-breaker device preceding the new device
and the CommsTool will ask for confirmation
of the new device location.
RETRIEVE LATEST FILE FROM PANEL
USING COMMSTOOL
On ComsTool.
'Device Configuration'
Inserting Device
*
1) Select the Device that follows the New device.
2) Click the INSERT button
3) Select the Newly inserted device.
4) Modify the Type, Sub-Type and Device Selection
to match the New fitted device.
5) Click the CHANGE button
CHECK LOOP MAP DETAILS IN AREA OF CHANGE.
** SAFE ADDRESSED LOOPS
EDIT LOOP MAP ON COMMS TOOL
PC TO MATCH THE PANEL'S LOOP
MAP
DEVICES DEFAULT TO SECTOR 1, ZONE 1 etc
THEREFORE THE LABELLING & CONFIGURATION
MUST BE EDITED TO SUIT THE SYSTEM
Deleting Device
Save the Device Configuration
page then Save The Commissioning
Tool Site File with a new name.
Transmit the new Configuration
to the Panel and Note any
Minor/Major Conflicts
Important Backup ALL Cards to the NVM
**Loop map edit codes:
– conn to panel End 1
0
251 – conn to panel End 2
252 – conn not available
255 – conn avail but not in
use ie o\cct , not connected
SELECT DEVICE TO BE DELETED
and DELETE
** SAFE ADDRESSED LOOPS
EDIT LOOP MAP ON PC TO MATCH
THE PRINT OUT FROM THE PANEL
Perform a Functional Test