Honeywell Gent Vigilon Plus Manual page 80

Loop panels
Table of Contents

Advertisement

S-Quad & S3 Mk2/Mk3
For Standard Panel Signals (No Voice Messages) set Low/Attn Tone AND
High/Message to 00. Also Ensure that Speech Operation is unticked.
To use Voice Messages (Voice Enabled Devices) set Low/Attn Tone to 00
and set the High/Message to the required Message. Ensure that Speech
Operation is ticked.
Codes: 00 = standard tone for signal
01 = message 1 (bell ring)
02 to 05 = voice message 2 to 5
Note: If no Sounder/Voice Devices are in this Sector the Low/Attn Tone
and High Message will have the value of FF
*
*
*
*
Sndr - Sector can be setup
E.g. Sector 1 Loop 2; on receipt of a sig 2 instruction, all 'sounders' will provide standard 'evac' attention tone
followed by message 5 in a loop and VAD/Strobes will flash with a 2 sec on/off rate
Warning – Do not use Voice Messages if you have a mix of Voice and
Non-Voice enabled devices in the same sector.
Sector
setup
For any Sounder to make a sound,
Audible On must be ticked against that
Signal.
If Speech is to be used, Speech
Operation must be ticked against that
Signal.
VAD/Str Actioned if ticked will flash any
VADs or Strobes for that Signal.
Note: A Combined Sounder/VAD must
have at least one output working.
Strobe period: (2 seconds
between Flashes)
Pre speech & post speech:
Gap between attention tone
and message

Hide quick links: