Connecting To A Ruggedcom Rp100 Or Rp110 - Siemens RUGGEDCOM WIN7251 Installation Manual

Table of Contents

Advertisement

RUGGEDCOM WIN7251
Installation Guide
Section 2.8.2, "Connecting the Data Adapter"
Section 2.8.3, "Assembling the PoE Connector"
Section 2.8.4, "Installing the Hazardous Location Kit"
Section 2.8.1

Connecting to a RUGGEDCOM RP100 or RP110

The RUGGEDCOM RP100 and RP110 are optional power injectors for powering and providing data to the
RUGGEDCOM WIN7251. The RUGGEDCOM RP100 and RP110 meet a wider temperature and voltage range than
the standardRUGGEDCOM WIN1010.
When the base station is connected to a RUGGEDCOM RP100 or RP110, make sure there is a solid connection
between the lightning protector and the base station. The following illustration details a typical installation.
NOTE
A shielded cable must be used and connected to local ground at both the base station and lightning
protector.
NOTE
The lightning protector must meet the necessary requirements of IEC/UL/CSA 60950-1. The clamping
voltage must also be less than 60 V and the protector must not activate when the voltage is less than
56 V. For more information about these requirements, contact Siemens Customer Support.
IMPORTANT!
Install the lightning protector and the RUGGEDCOM RP100/RP110 as close as possible.
Figure 9: Typical Outdoor Installation
1. RUGGEDCOM WIN7251    2. Shielded Cable    3. Ground Connection    4. Lightning Protector    5. RUGGEDCOM RP100/RP110    6. Drain
Wire (Shielded)
For more information about the RUGGEDCOM RP100 or RP110, refer to the RUGGEDCOM RP100 Installation Guide
or the RUGGEDCOM RP110 Installation Guide.
Connecting to a RUGGEDCOM RP100 or RP110
1
6
3
2
4
3
Installing the Base Station
5
3
Chapter 2
17

Advertisement

Table of Contents
loading

Table of Contents