9. Electric expansion valve control circuit
POWER P.W.B.
CN15
6
5
4
3
Electric
2
expansion
valve
1
• To drive the expansion valve, use the B-12 V output. Use a 4-phase coil and feed power to the phases
1 and 2, then switch over the filed poles to control the opening of the valve.
• The reference between conducting phase switch over direction and the open/close direction are
shown in Table 9-1. When the power is turned on, approx. 0.9 V is applied to the CN15 and the pins
(1 to 4) and when no power is supplied, 12 V is applied. When the power is reset, the expansion
valve starts initial operation for 5 to 10 seconds.
• During the initial operation, measure each pin of the CN15 (1 to 4) with a multimeter. If no change
is found around 0.9 V or 12V in this step, the expansion valve or the micro computer has failure.
• The logic waveform during the operating of the expansion valve is shown in Fig. 9-2.
CN15
Pin No.
Operation mode
Pin No.
B-12V B-12V
B-12V
R401
1 8
15
14
2
3
10
11
6
7
+
4 5
12 13
C401
IC6
B-0V
Lead
wire
1
2
3
ON
ON
OFF
White
Yellow
OFF
ON
ON
Orange
OFF
OFF
OFF
Blue
OFF
OFF
OFF
1 2 3 4 5 6 7 8 VALVE CLOSE
8 7 6 5 4 3 2 1 VALVE OPEN
50ms.
5V
R403 R404
PQ401
PQ402
PQ403
PQ404
CN4B
Fig. 9-1
Table 9-1
Drive status
4
5
6
7
OFF
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
OFF
ON
ON
75ms.
200ms.
Fig. 9-2
– 55 –
MAIN P.W.B.
Microcomputer
R293
1
11
39
Valve4
R294
10
2
40
Valve3
R295
4
8
41
Valve2
R296
3
9
42
Valve1
CN4A
8
ON
OFF
OFF
ON
12V
0.9V