Multiple Units Connected To One Remote Thermostat (2800 Series) - GE Zoneline Generation III 2800 Series Technical Service Manual

Table of Contents

Advertisement

All manuals and user guides at all-guides.com

Multiple Units Connected to One Remote Thermostat (2800 Series)

One remote control thermostat may be used to control multiple resistance heat Zoneline units, however the
units may not be wired direct. Since each Zoneline unit has an integral transformer, direct wiring can result
in a "bucking" or boosting" voltage condition, and is in violation of the National Electric Code. The diagram
below shows the correct wiring for such an installation through the use of fi eld supplied isolation relays.
Remote Control (Low Voltage) Wiring
One stage thermostat controlling 3 Zoneline units.
Resistance heat Zoneline 2800 series units.
(Not Applicable on Heat Pump Units.)
Field Supplied Relay Specifi cations
– 29 –

Advertisement

Table of Contents
loading

This manual is also suitable for:

Zoneline generation iii 3800 series

Table of Contents