17.4

Error Codes Table

Diagnosis display
Abnormality / Protection control
H00
No abnormality detected
H12
Indoor/Outdoor capacity unmatched
H15
Outdoor compressor temperature sensor
abnormality
H23
Indoor refrigerant liquid temperature
sensor abnormality
H42
Compressor low pressure abnormality
H62
Water flow switch abnormality
H63
Refrigerant low pressure abnormality
H64
Refrigerant high pressure abnormality
H70
Back-up heater OLP abnormality
H72
Tank sensor abnormal
H76
Indoor - control panel communication
abnormality
H90
Indoor / outdoor abnormal
communication
H91
Tank heater OLP abnormality
H95
Indoor/Outdoor wrong connection
H98
Outdoor high pressure overload
protection
H99
Indoor heat exchanger freeze prevention
F12
Pressure switch activate
F14
Outdoor compressor abnormal revolution
F15
Outdoor fan motor lock abnormality
F16
Total running current protection
F20
Outdoor compressor overheating
protection
F22
IPM (power transistor) overheating
protection
F23
Outdoor Direct Current (DC) peak
detection
F24
Refrigeration cycle abnormality
F25
Cooling / Heating cycle changeover
abnormality
F27
Pressure switch abnormality
F36
Outdoor air temperature sensor
abnormality
F37
Indoor water inlet temperature sensor
abnormality
F40
Outdoor discharge pipe temperature
sensor abnormality
F41
PFC control
F42
Outdoor heat exchanger temperature
sensor abnormality
Abnormality Judgement
90s after power supply
Continue for 5 sec.
Continue for 5 sec.
Continue for 1 min.
4 times occurrence within
20 minutes
Continue for 5 sec.
Continue for 60 sec.
Continue for 5 sec.
> 1 min after starting operation
Continue for 60 sec.
4 times occurrence within
20 minutes
4 times occurrence within
20 minutes
2 times occurrence within
30 minutes
3 times occurrence within
20 minutes
4 times occurrence within
30 minutes
3 times occurrence within
30 minutes
7 times occurrence
continuously
2 times occurrence within
20 minutes
4 times occurrence within
30 minutes
Continue for 1 min.
Continue for 5 sec.
Continue for 5 sec.
Continue for 5 sec.
4 times occurrence within
10 minutes
Continue for 5 sec.
94
Primary location to verify
Indoor/outdoor connection wire
Indoor/outdoor PCB
Specification and combination table in
catalogue
Compressor temperature sensor
(defective or disconnected)
Refrigerant liquid temperature sensor
(defective or disconnected)
Outdoor pipe temperature sensor
Clogged expansion valve or strainer
Insufficient refrigerant
Outdoor PCB
Compressor
Water flow switch
Outdoor low pressure sensor (defective
or disconnected)
Outdoor high pressure sensor
(defective or disconnected)
Back-up heater OLP
(Disconnection or activated)
Tank sensor
Indoor - control panel
(defective or disconnected)
Internal / external cable connections
Indoor / Outdoor PCB
Tank heater OLP
(Disconnection or activated)
Indoor/Outdoor supply voltage
Outdoor high pressure sensor
Water pump or water leakage
Clogged expansion valve or strainer
Excess refrigerant
Outdoor PCB
Indoor heat exchanger
Refrigerant shortage
Pressure switch
Outdoor compressor
Outdoor PCB
Outdoor fan motor
Excess refrigerant
Outdoor PCB
Compressor tank temperature sensor
Clogged expansion valve or strainer
Insufficient refrigerant
Outdoor PCB
Compressor
Improper heat exchange
IPM (Power transistor)
Outdoor PCB
Compressor
Insufficient refrigerant
Outdoor PCB
Compressor low compression
4-way valve
V-coil
Pressure switch
Outdoor air temperature sensor
(defective or disconnected)
Water inlet temperature sensor
(defective or disconnected)
Outdoor discharge pipe temperature
sensor (defective or disconnected)
Voltage at PFC
Outdoor heat exchanger temperature
sensor (defective or disconnected)