NAPCO Continental Access Accelaterm Installation And Service Manual
NAPCO Continental Access Accelaterm Installation And Service Manual

NAPCO Continental Access Accelaterm Installation And Service Manual

Eight / sixteen door access control panel

Advertisement

Quick Links

Accelaterm
®
Eight / Sixteen Door
Access Control Panel
Installation and Service Manual
A NAPCO SECURITY GROUP COMPANY
355 Bayview Avenue, Amityville, NY 11701
Phone: 631-842-9400
Fax: 631-842-9135
www.cicaccess.com
Publicly traded on NASDAQ
Symbol: NSSC
© NAPCO 2013
WI1989
draft 49
02/13
®
1
Accelaterm
Installation and Service Manual

Advertisement

Table of Contents
loading

Summary of Contents for NAPCO Continental Access Accelaterm

  • Page 1 Accelaterm ® Eight / Sixteen Door Access Control Panel Installation and Service Manual A NAPCO SECURITY GROUP COMPANY 355 Bayview Avenue, Amityville, NY 11701 Phone: 631-842-9400 Fax: 631-842-9135 www.cicaccess.com Publicly traded on NASDAQ Symbol: NSSC © NAPCO 2013 WI1989 draft 49 02/13 ®...
  • Page 2 Continental Ac- cess, 355 Bayview Avenue, Amityville, NY 11701. 631-842-9400 A NAPCO SECURITY TECHNOLOGIES COMPANY I M P O R T A N T W I R I N G M E T H O D S...
  • Page 3 THE INSTALLATION AND SERVICE OF THIS PRODUCT MUST BE PERFORMED BY QUALIFIED SERVICE PERSONNEL AND SHOULD CONFORM TO ALL LOCAL CODES. The lightning flash with arrowhead symbol, within an equilateral trian- gle, is intended to alert the user to CAUTION presence un-insulated RISK OF ELECTRIC SHOCK...
  • Page 4: Table Of Contents

    TABLE OF CONTENTS ACCELATERM DESCRIPTION ..........................5 IMPORTANT SAFETY INFORMATION ......................6 CONFIGURATION ..............................7 Capacities ................................7 Communication ..............................7 Memory ................................7 INSTALLATION ..............................8 Cabinet Mounting ............................. 10 Cable and Wiring Categories ..........................11 Accessory Conduit Knockouts ......................... 11 Grounding Accessory Drain and Shield Wires ....................
  • Page 5: Accelaterm Description

    DESCRIPTION 115VAC/60Hz (USA) and 230 VAC/50Hz EU. With ACCELATERM DESCRIPTION built-in overcurrent protection, this Access Control panel The Accelaterm is a fully programmable, self contained, meets the requirements for Energy-Limited installations. 8/16* door access control panel that offers users flexibility, expandability, and simplicity.
  • Page 6: Important Safety Information

    DESCRIPTION Replace the lithium backup battery on the Interface Board IMPORTANT SAFETY INFORMATION with a Rayovac "BR1225E" coin cell. Use of another bat- The Accelaterm has been evaluated by UL as a Stand-Alone tery may present a risk of fire or explosion. Access Control System (Burglary and Fire Alarm features have not been evaluate by UL).
  • Page 7: Configuration

    CONFIGURATION CICP2800PMBD Base Processor 8MB SRAM Memory Expansion Memory Module Modules (model CICP18MEM8MB; up to two can be installed into the CICP2800RLYBD Relay PC Board CICP2800PMBD Base Processor Normally-open, Memory Module) normally-closed circuits with op- tional "wet" or "dry" outputs CICP18ACCNETBD Ethernet PCB CICP2800RS485BD RS-485 Repeater PC Board...
  • Page 8: Installation

    INSTALLATION The following warnings are designed for the safety of the Ac- INSTALLATION celaterm install/service technician and for the continued proper Only qualified service personnel familiar with all local building function of the Accelaterm unit. codes should attempt this installation. Take appropriate safe- guards to avoid unintentional operation by employees and About This Manual maintenance personnel working about the premises.
  • Page 9 INSTALLATION • Determine the directions of the cabling conduit exiting Installation Preparation the Accelaterm cabinet. Confirm sufficient access to First, select a mounting location within a secure, limited ac- ceilings and/or walls before fitting the conduit lengths. cess area (see Figure 2). Make note of the wall construction type to which the cabinet will be secured.
  • Page 10: Cabinet Mounting

    INSTALLATION 3. Place the Accelaterm cabinet out of the way. Cabinet Mounting Inspect the mounting surface around the proposed installation 4. Drill pilot holes to the required depth and size for the site. The mounting surface must be capable of supporting 38 mounting screws.
  • Page 11: Cable And Wiring Categories

    INSTALLATION Block (see page 12). The power cabling is delivered to the Cable and Wiring Categories Accelaterm through a knockout located on the lower right side The wiring and cabling for the Accelaterm are divided into cabinet wall (see Figure 5). The 3/4 inch knockout accepts three categories: EIA standard conduit connectors.
  • Page 12: Power Connections

    POWER CONNECTIONS POWER CONNECTIONS Table 1 lists the incoming AC source voltage connections to the AC Input Power Terminal Block in the USA (see Table 2 for Europe). AC Power Source Grounding Note : Knockouts for conduit Fittings are located on the back of the metal housing and can be used if "hidden cable"...
  • Page 13 POWER CONNECTIONS CICP2800EXPRDBD 8 Reader Expansion Board connector (Use Clear Tubing for these wires) Green LED AC power "ON" Battery indicator light Compartment Class 1 Wiring Line Connection to Connection Ground Neutral branch circuit Connection to Connection branch circuit IMPORTANT: Keep power-limited wiring AT LEAST 1/4" (one-quarter of an inch) away from the top of the ex- posed printed circuit boards, and away from the Battery Compartment.
  • Page 14: Wiring Diagram

    WIRING DIAGRAM Accelaterm Wiring Diagram The following descriptions in this manual reference the Ac- The Accelaterm circuit board (see Figure 8) provides wiring celaterm main circuit board, shown below, and use cutaway terminal strips for external access control devices (card read- drawings to identify specific locations on the circuit board.
  • Page 15: Door Connections

    DOOR CONNECTIONS Table 4 lists the cable gauge-vs.-length requirements for DOOR CONNECTIONS proper operation the Accelaterm and a Wiegand/Proximity Inputs from Card Readers, Keypad/Card Readers and Door Reader. Alarms connect to the Accelaterm via the terminal strips on the left and right side of the board labeled RDR1 through RDR16. Table 4 - Cable Requirements for Wiegand/Proximity Readers Wiegand/Proximity Reader Connections...
  • Page 16 DOOR CONNECTIONS Wiegand Proximity Reader Black Brown White Terminal Green Strip Drain Wire/Shield Accelaterm Cabinet Ground Post Accelaterm Circuit Board Figure 9 - Wiegand/Proximity Reader Connection to Accelaterm Board ® Accelaterm Installation and Service Manual...
  • Page 17: Magnetic Stripe Reader Connection

    DOOR CONNECTIONS Magnetic Stripe Reader Connection Magnetic Stripe Reader Cable Requirements not evaluated by UL Magnetic Stripe Readers require a 5-conductor cable between Magnetic Stripe Readers ( ) connect to the Accelaterm and the particular unit (see Figure 10). Do not terminal strips DR (see Figure 10).
  • Page 18: Door Status Sensor Connection

    DOOR CONNECTIONS Door Status Sensor Connection Door Status Sensor Cable Requirements Door Status sensors connect to the Accelaterm through two ter- Door Status sensors require a 22AWG, 2-conductor, stranded, minal strips labeled RDRx (see Figure 11). shielded, cable with drain wire between the Accelaterm and the particular unit (see Figure 11).
  • Page 19: Request-To-Exit (Bypass) Sensor Connection

    DOOR CONNECTIONS Request-to-Exit (Bypass) Sensor Connection Request-to-Exit Sensor Cable Requirements Request-to-Exit sensors (also known as Bypass sensors) work in conjunction with Door Status Sensors to provide complete Request-to-Exit sensors require a 22AWG, 2-conductor, facility entry and exit control. The Request-to-Exit sensor stranded, shielded, cable with drain wire between the Ac- input connects to the same Accelaterm terminal strip (RDRx) celaterm and the particular unit (see Figure 12).
  • Page 20: Relay Connections

    RELAY CONNECTIONS be located near the Access Control Panel. Some models carry RELAY CONNECTIONS connections to meet some considerations for use with a Fire Introduction Alarm Control Panel. (FACP) The Accelaterm Relay Board provides 17 relays with Nor- mally-Open, Common, and Normally-Closed contact connec- Console Relay tions from each relay.
  • Page 21 RELAY CONNECTIONS Lock Power Examples 12/24 to 28 VDC 12/24 to 28 V Power Supply AC/DC (–) (–) 1. Fail-Safe EM Lock (–) (–) 2. Fail-Secure Electric Strike (–) 3. Fail-Safe EM Lock (–) 4. Fail-Safe Electric Strike Figure 13 - Lock Power Example Lock 1: A fail-safe electro-mechanical (EM) lock powered mended lock current rating is 2A or less.
  • Page 22: Expansion Board Connections

    EXPANSION BOARD CONNECTIONS pairs of conductors for two power-limited circuits. EXPANSION BOARD CONNECTIONS power supply may be one or two UL603 or UL294 listed Internally-Routed Power for units. Normally battery-backed, these may be 12VDC or 24 Locks 5-8 and 13-16 to 28VDC.
  • Page 23: Accessory Power

    ACCESSORY POWER ACCESSORY POWER The ACCESSORY POWER terminal strip (labeled "JP2" and "ACC PWR OUT") provides battery backed +12VDC power outlets for auxiliary devices. This terminal strip is located in the lower middle of the Relay Board. Table 12 lists the ACC PWR OUT terminal strip pin numbers and their associated functions.
  • Page 24: Accessory Alarm Connections

    ALARM CONNECTIONS alarm. ACCESSORY ALARM CONNECTIONS 2. Install R 1 in parallel with the alarm contacts (see Figure Eight accessory supervised alarm inputs are located on the 15). Accessory ALARM terminal strip located on the upper left 3. Install R2 in series with the alarm input conductor. corner of the Accelaterm circuit board (see Figure 15).
  • Page 25: Communication

    COMMUNICATION CONNECTIONS Installing the isolated CICP2800RS485BD board allows di- COMMUNICATION rect connection with other Access Control Panels upstream Each Accelaterm may communicate with the Host Computer and downstream on a 4-wire Repeater String. This allows for or Server via an Ethernet connection. Or each Accelaterm high data rates and industry-leading isolation from very high- may communicate through a high speed full-duplex (4-wire) energy transients, adding ground-loop isolation to already...
  • Page 26: Networking

    COMMUNICATION CONNECTIONS See "Clear Memory and Force Download to Panel" on page Networking The Accelaterm can be networked with a maximum of 62 other Accelaterm units or other Continental Access access Communication LED Functions control devices (Superterm, Turbo Superterm, Smarterm, Miniterm and Microterm).
  • Page 27: Functions Of The '485 Data Pair Connections

    COMMUNICATION CONNECTIONS Functions of the ‘485 Data Pair Connections Note: A (+) is always connected to a (+), and a (-) always to a (-). A Transmitter is always connected to a Receiver. Up- Differential stream cables head toward the Server; downstream cables head Transmitter Data away from the Server.
  • Page 28: Led Diagnostics

    LED DIAGNOSTICS LED Diagnostics The Accelaterm circuit board uses LED's to indicate the presence of a particular voltage and EIA/TIA-232 signals. Figure 20 shows the LED position on the Accelaterm circuit board and the individual LED functions. Table 14 - LED Diagnostic Functions Marking Function Notes...
  • Page 29 LED DIAGNOSTICS Charger/Isolator Board: CICP2800PCHGBD 12 Volt DC Output from board, either from Power Supply or from Backup Battery 12 Volt DC Into board from Power Supply. Does not light if operating on Backup Battery Figure 21 - LED Diagnostics: Charger/Isolator Board (CICP2800PCHGBD) Processor/Memory Board: CICP2800PMBD (Red) Reset 5 Volt DC Passed to this...
  • Page 30: Overcurrent Protection

    CIRCUIT PROTECTION OVERCURRENT PROTECTION Transient Protection Nearby lightning discharges induce high-voltage transients into the field wiring of electronic equipment. The Accelaterm External Circuits Access Control Panel provides protection from high-voltage The Accelaterm provides 12VDC power to the badge readers, transients at all field wiring terminals. This includes all accessory devices, and electric locks.
  • Page 31: Maintenance

    MAINTENANCE power is lost and the backup batteries are discharged. These MAINTENANCE cells ensure that the correct time is set and the database is held for instant availability when power is restored. The correct Coin Cell Activation time and the database will normally be loaded from the Host The Clock/Calendar chip on the Interface board is backed by a Server in a small fraction of a minute.
  • Page 32: Specifications

    SPECIFICATIONS Specifications Quantity Comments CardAccess Compatibility Full function on or off line 200K Base 4M Memory/ 5-digit Cards Card Capacity 650K Full 20M Memory/19-digit Cards 4M Base Database RAM One Option Memory Module Each option Module adds 8M Two Option Memory Modules Eight Base Unit Card Reader Capacity...
  • Page 33 SPECIFICATIONS Environmental and Regulatory Quantity Comments Temperature Range Operating 32 - 120°F (0 - 49°C) Temperature Range Storage 32 - 149°F (0 - 65°C) Relative Humidity 0% to 85% non-condensing UL294 Access Control (USA) 115VAC 60Hz only Compliance CE Mark (EU) Configurable from Host Quantity Comments...
  • Page 34: Power Ratings

    SPECIFICATIONS POWER RATINGS The Accelaterm contains a power supply that switches between 120VAC/60Hz for the USA, or 230VAC/50Hz for the EU. Current Voltage Input (Maximum) 115VAC 2.0 Amperes 230VAC 1.0 Amperes Output Rating: 12V regulated maximum 5A. Standby Current Combined Standby Current Charger Board + Interface Board + 95mA + 30mA for Battery...
  • Page 35: Appendix A: Cicp18Accnetbd Ethernet Board Installation Instructions

    APPENDIX A CICP18ACCNETBD INSTALLATION The CICP18ACCNETBD Ethernet board is mounted in the Ac- celaterm Interface board (see the Accelaterm installation instruc- Squeeze Here tions WI1989 for more information regarding the Interface board installation). Prior to opening the Ethernet board package or touching anything inside the control panel enclosure, discharge any static electricity from your body or clothing.
  • Page 36 APPENDIX A Be sure to tighten the cable clamp screws securing both the Ethernet cable and the braided shield to the panel enclosure. 8. Plug the Ethernet cable into the Ethernet board receptacle. 9. Re-connect power to the system, including the battery wires. Verify that the OK lamp (LED) on the Interface board blinks on and off once per second.
  • Page 37: Appendix B: Cicp2800Exprdbd 8 Reader Expansion Board Installation Instructions

    APPENDIX B CICP2800EXPRDBD Eight (8) Reader Expansion Board Installation Instructions GENERAL INFORMATION and separate from the logic power. The standard version Accelaterm provides access control Each of the 8 alarm inputs on the main board may be config- functions for eight doors and eight card readers. The plug-in ured as supervised alarms (requiring termination resistors), eight reader expansion board adds capability for eight more or standard alarms (requiring plain electrical contacts).
  • Page 38 APPENDIX B into the 6 threaded standoff locations in the Accelaterm in- lock power through the Accelaterm Relay Board. terface board shown on page 1. Then plug the To the right of the center line on the Relay Board, find JP4 CICP2800EXPRDBD 8 Reader Expansion Board into the con- marked LOCK...
  • Page 39: Appendix C: Cicp2800Rs485Bd Repeater Board Installation Instructions

    APPENDIX C CICP2800RS485BD RS-485 Repeater Board Wiring Instructions The CICP2800RS485BD RS-485 Repeater Board allows commu- (To the nication between a host computer and Accelaterms that do not have network) access to the network via the CICP18ACCNETBD. Multiple Ac- celaterms can be connected downstream through the 4-wire RS485 bus, as shown in the wiring diagram.
  • Page 40 APPENDIX C CICP2800RS485BD INSTALLATION 4. Align the Repeater board plug with the Interface board recep- is mounted into CICP2800RS485BD RS-485 Repeater Board tacle "JP1" as shown in Fig. 4 below. the Accelaterm Interface board (see the Accelaterm installation instructions WI1989 for more information regarding the Interface board installation).
  • Page 41 NOTES ® Accelaterm Installation and Service Manual...
  • Page 42: Warranty / Terms & Conditions

    WARRANTY / TERMS & CONDITIONS Standard Terms of Sale • If customer believes an invoice to be in error, cus- tomer shall notify Continental of the error within Ordering thirty (30) days. Orders for Continental products may be placed by •...
  • Page 43 riod of one year from date of shipment of the product no Circumstances will Continental be liable for direct, to purchaser. The warranty on 3rd party equipment indirect or consequential damages of any kind. such as terminals, printers, and communications de- vices shall be 1 year from date of shipment.