Download Print this page

Veris Industries E50C2 Installation Manual page 15

Compact power and energy meter
Hide thumbs Also See for E50C2:

Advertisement

Installation Guide
Power Monitoring
E50B1, E50C2, E50C3
UI for Setup (cont.)
To Setup p. 1 "S PWR"
Back
SPLOS
Phase
Loss
Back
SPULS
Pulse
Output
Back
SDMND
Demand
Back
S DIS
Display
Units
Back
SPASS
Setup
Passwords
To Setup page 1 "S CT", "S COM",
or "S BAC" depending on model
† When leaving this parameter screen using the right button ( ), the display will
briefly indicate "SAvEd)" to confirm that any changes made have been accepted.
ZL0103-0C
Page 15 of 26
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Shop for Power Metering products online at:
VOLTS
IMBAL
--------
--------
0.10
0.25
Next
Max
mS/P
PPS
Wh/P
--------
--------
--------
500
1
10000
250
2
1000
100
5
100
50
10
10
25
20
10
50
Next
BDS
INTRV
--------
6
SEC
5
--------
4
00900
3
2
Next
1
UNITS
Set Display Units: +/- to switch between:
--------
IEEE – VLL VLN W VAR VA Units.
IEEE
IEC -
IEC
Next
SETUP
RESET
--------
--------
00000
00000
Next
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
PowerMeterStore
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
www.
Set Phase Loss:
VOLTS - Phase Loss Voltage: The fraction of the system
voltage below which Phase Loss Alarm is on. For system
types with neutral, the Line to Neutral voltage is also
calculated and tested. If the System Voltage is 600 and the
fraction is set to 0.10, then the Phase Loss threshold will be
60 volts.
IMBAL - Phase Loss Imbalance: The fractional difference
in Line to Line voltages above which Phase Loss Alarm is
on. For system types with neutral, the Line to Neutral
voltages are also tested. For system types 1+N (10) and 2
(11) , imbalance is not tested.
Set Pulse:
The System Type , CT size, PT Ratio, and System Voltage must
all be configured before setting the Pulse Energy. If any of these
parameters are changed, the meter will hunt for a new Pulse
Duration, but will not change the Pulse Energy. If it cannot find a
solution, the meter will display the wrench, show "ConF" in the
ALARM -> PULSE screen, and enable Energy pulse output
configuration error bit in the Modbus Diagnostic Alert Bitmap (if
equipped).
Wh/P - Set Pulse Energy: In Watt Hours (& VAR Hours, if
present) per Pulse. When moving down to a smaller energy, the
meter will not allow the selection if it cannot find a pulse duration
that will allow the pulse output to keep up with Theoretical
Maximum System Power (see S_PWR screen). When moving
up to a larger energy, the meter will jump to the first value where
it can find a valid solution.
mS/P – Minimum Pulse Duration Time: This read only value
is set by the meter to the slowest duration (in mS per closure)
that will keep up with the Theoretical Maximum System Power.
The open time is greater than or equal to the closure time. The
maximum Pulses Per Second (PPS) is shown in yellow.
Set Demand Interval:
INTRV - The number of Sub-Intervals (1 to 6) in a
Demand Interval. Default is 1 (block demand).
SEC - Sub-Interval length in seconds. Default is
900 (15 minutes). Set to 0 for external sync-to-
comms (Modbus units only).
U
V
P
Q
S Units.
Set Passwords:
SETUP - The Password to enter the SETUP menu.
RESET - The Password to enter the RESET menu.
09141
1.888.610.7664
.com
TM

Advertisement

loading

This manual is also suitable for:

E50b1E50c3E50h5E50h2E51c2E51c3