Installation Guide
Power Monitoring
E50B1, E50C2, E50C3
Solid State Output
User Interface (UI)
Menu Abbreviations
Defined
ZL0103-0C
Page 11 of 26
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Shop for Power Metering products online at:
The E50 have one normally open (N.O.) KY Form A output and one normally closed (N.C.) output.* One is dedicated to energy
(Wh), and the other to Alarm. The E50B1 also provides an additional N.O. reactive energy (VARh) contact. See the Setup section for
configuration information.
Over-Current Protective
Device** (not supplied)
≤ 100 mA
E50B1 only
+
S
Alarm
Energy
Output
The solid state pulse outputs are rated for 30 VAC/DC nom.
Maximum load current is 100mA at 25°C. Derate 0.56 mA per °C above 25°C.
* While the relay used for the Phase Loss contact is Normally Closed (contacts are closed when the meter is not powered), closure indicates the presence of an
alarm; either loss of phase, when the meter is powered, or loss of power when the meter is not. The contacts are open when the meter is powered and no phase
loss alarm conditions are present
** Use an over-current protective device rated for the short circuit current at the connection point.
The user can set the display mode to either IEC or IEEE notation in the SETUP menu.
Main Menu
IEC
IEEE
D
D
Demand
MAX
M
Maximum Demand
P
W
Present Real Power
Q
VAR
Present Reactive Power
S
VA
Present Apparent Power
A
A
Amps
UAB, UBC, UAC
VAB, VBC, VAC
Voltage Line to Line
V
VLN
Voltage Line to Neutral
PF
PF
Power Factor
U
VLL
Voltage Line to Line
HZ
HZ
Frequency
KSh
KVAh
Accumulated Apparent
Energy
KQh
KVARh
Accumulated Reactive
Energy
KPh
KWh
Accumulated Real Energy
PLOSS
PLOSS
Phase Loss
LOWPF
LOWPF
Low Power Factor Error
©2014 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
PowerMeterStore
Other companies' trademarks are hereby acknowledged to belong to their respective owners.
www.
Power Source
~
3-30 VDC
=
LOAD
6-30 VAC
≤ 100 mA
Power Source
~
3-30 VDC
=
6-30 VAC
LOAD
≤ 100 mA
Power Source
~
3-30 VDC
=
LOAD
6-30 VAC
Description
IEC
F ERR
I OVR
V OVR
PULSE
_PHASE
ALERT
INFO
MODEL
OS
RS
SN
RESET
PASWD
ENERG
DEMND
Main Menu
IEEE
Description
F ERR
Frequency Error
I OVR
Over Current
V OVR
Over Voltage
PULSE
kWh Pulse Output Overrun
(configuration error)
_PHASE
Summary Data for 1, 2, or 3
active phases
ALERT
Diagnostic Alert Status
INFO
Unit Information
MODEL
Model Number
OS
Operating System
RS
Reset System
SN
Serial Number
RESET
Reset Data
PASWD
Enter Reset or Setup
Password
ENERG
Reset Energy Accumulators
DEMND
Reset Demand Maximums
09141
1.888.610.7664
.com
TM