INSTALLATION

Turn the power OFF at the circuit breaker before installing the sensor.
WS
Wall Switch
1. Connect the existing wires in the wall box to the sensor flying leads. (See
Wiring Directions at right).
• Do not allow bare wire to show below connector.
• The ground wire must be tightly grounded for the unit to operate
properly.
2. Attach the sensor to the wall by mounting it in the wall box with the two
mounting screws provided.
3. Turn ON power at the circuit breaker.
4. Test the sensor using the procedure in the Sensor Adjustments section.
There is an initial warm-up period after installation. It may take up to a
minute before the load turns ON due to a sensor warm-up period during
initial power-up (this occurs during installation only). The load turns ON
after the warm-up period ends if the sensor detects motion.
Rapid successive pressing of the ON/OFF button causes a delay in
function. A single press of the button causes an immediate response. If the
button is pressed again within 2 seconds, the switch ignores it. Wait at least
two seconds between button presses.
5. Install industry standard decorator wall switch cover plate (not included).
Call 800.879.8585 for Technical Support
CAUTION
Wall
Junction Box